F04 - F04 Fireguard License Portable Fire Extinguishers Questions and Answers 1 — Questions and Answers
Question 1: A Fireguard conducting a monthly 'quick check' on a portable fire extinguisher must verify several conditions. Which of the following is NOT a required part of this monthly inspection?
- Weighing the extinguisher to check the agent level. (Correct answer)
- Ensuring the extinguisher is in its designated place and is not obstructed.
- Checking that the pressure gauge is in the operable (green) range.
- Verifying that the safety pin is in place and the tamper seal is not broken.
Correct answer: Weighing the extinguisher to check the agent level.
The monthly 'quick check' is a visual inspection that can be done by a trained individual and does not require a Certificate of Fitness. It includes checking for accessibility, ensuring the pressure gauge is in the green, and verifying the pin and seal are intact. Weighing the extinguisher is part of a more detailed annual maintenance check performed by a licensed professional, not the simple monthly visual inspection.
Question 2: While on patrol at a temporary outdoor concert, a Fireguard discovers a small fire in a trash can, fueled by paper and cardboard. Which class of fire extinguisher is the most appropriate to use in this situation?
- Class K
- Class B
- Class A (Correct answer)
- Class C
Correct answer: Class A
The fire involves ordinary combustible materials like paper and wood, which are classified as a Class A fire. A Class A fire extinguisher, typically containing water or certain dry chemicals, is designed for this type of fire. Class B is for flammable liquids, Class C is for electrical fires, and Class K is for cooking oils and fats.
Question 3: A Fireguard must use the P.A.S.S. method to operate a portable fire extinguisher. What does the 'A' in the P.A.S.S. acronym stand for?
- Activate the alarm before approaching the fire.
- Assess the size of the fire to ensure it is safe to fight.
- Alert others in the immediate vicinity.
- Aim the nozzle at the base of the fire. (Correct answer)
Correct answer: Aim the nozzle at the base of the fire.
The P.A.S.S. method is an acronym for the proper operation of a fire extinguisher. The steps are: Pull the pin, Aim the nozzle at the base of the fire, Squeeze the handle, and Sweep from side to side. Aiming at the base is crucial because it targets the fuel source of the fire.
Question 4: According to FDNY regulations, how should portable fire extinguishers be mounted?
- The top of the extinguisher must be no more than 3 feet from the floor.
- The bottom of the extinguisher must be resting securely on the floor.
- The top of the extinguisher must be no more than 5 feet from the floor, and the bottom no less than 4 inches from the floor. (Correct answer)
- The extinguisher must be placed in a cabinet with the handle at exactly 4 feet from the floor.
Correct answer: The top of the extinguisher must be no more than 5 feet from the floor, and the bottom no less than 4 inches from the floor.
FDNY regulations specify mounting heights to ensure extinguishers are accessible. The top of the extinguisher should not exceed 5 feet above the floor, and there must be a minimum clearance of 4 inches between the bottom of the extinguisher and the floor. They should never be placed directly on the floor.
Question 5: A fire breaks out involving energized electrical equipment in a sound booth at a public assembly. Which of the following extinguisher types would be dangerous to use on this fire?
- Carbon Dioxide (CO2)
- Water-based (Correct answer)
- Multi-purpose Dry Chemical (ABC)
- Halon or other clean agent
Correct answer: Water-based
A fire involving energized electrical equipment is a Class C fire. Using a water-based extinguisher is extremely dangerous because water conducts electricity, which can lead to electrocution and potentially spread the fire. CO2, dry chemical, and clean agent extinguishers are non-conductive and are appropriate for Class C fires.
Question 6: During a pre-event inspection at a temporary place of assembly, you notice that a fire extinguisher's tag indicates its last annual professional service was 14 months ago. What is the correct course of action?
- Note it in the logbook and check it again next month.
- Assume the tag is wrong if the pressure gauge is in the green.
- Immediately report the deficient extinguisher to a supervisor and ensure it is replaced before the event begins. (Correct answer)
- Perform a quick check yourself and initial the tag if it looks okay.
Correct answer: Immediately report the deficient extinguisher to a supervisor and ensure it is replaced before the event begins.
Portable fire extinguishers must be professionally serviced annually. An extinguisher that is 14 months past its last service date is not in compliance and may not be reliable. The Fireguard's duty is to identify this hazard and report it immediately to ensure the safety of the assembly by having the unit replaced with a properly serviced one.