F-01 Fireguard System Impairment Procedures Flashcards
7 cards from real F-01 practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 F-01 Fireguard System Impairment Procedures flashcards as text
When a sprinkler system is placed out of service for maintenance, the fireguard must notify which agency first?
Answer: The Fire Department and the Bureau of Fire Prevention
FDNY and the Bureau of Fire Prevention must be notified whenever a fire suppression system is impaired.
A fire watch patrol during a system impairment must be conducted at minimum every:
Answer: 30 minutes
FDNY regulations require a fire watch patrol at least every 30 minutes during any system impairment.
Which document must the fireguard maintain to record all fire watch patrols during a system impairment?
Answer: Impairment log or fire watch log
An impairment log or fire watch log documenting time, route, and findings must be kept throughout the impairment.
If a fireguard discovers a new fire hazard during a fire watch patrol, what is the immediate first step?
Answer: Alert occupants and notify the fire department immediately
Immediate notification of occupants and the fire department is required upon discovery of any fire hazard.
Who is authorized to restore a fire suppression system to service after an impairment?
Answer: A licensed sprinkler contractor or qualified maintenance personnel
Only a licensed sprinkler contractor or qualified maintenance personnel may restore an impaired suppression system.
Which area should the fireguard pay particular attention to during a fire watch when a dry-pipe sprinkler system is impaired in winter?
Answer: Cold or unheated spaces where pipes could freeze if wet-pipe backup is used
During winter, unheated areas are especially vulnerable to pipe freezing issues if temporary wet-pipe measures are introduced.
An impairment tag (also called an impairment coordinator tag) must be attached to:
Answer: The control valve that has been shut off
The impairment tag must be attached directly to the control valve that was closed to identify the impaired section.