Under NFPA 25, the maximum time a sprinkler system should remain impaired before escalating notifications is:
Answer: 10 hours
NFPA 25 recommends that impairments lasting more than 10 hours require additional management notification and heightened precautions.
Temporary fire protection measures during an impairment may include all of the following EXCEPT:
Answer: Disabling the building's fire alarm system
Disabling the fire alarm system would increase risk; all other measures reduce hazards during the impairment period.
Who is ultimately responsible for authorizing a fire protection system impairment in a building?
Answer: The Impairment Coordinator or designated building authority
The Impairment Coordinator or the designated building authority has the responsibility and authority to approve and oversee impairments.
When hot work must be performed in an area with an impaired sprinkler system, the Impairment Coordinator should:
Answer: Require a hot-work permit and continuous fire watch during the work
A hot-work permit and a dedicated fire watch are required to mitigate ignition risk when the sprinkler system cannot provide suppression.
The Impairment Coordinator should ensure that impairment tags are color-coded, with red typically indicating:
Answer: An emergency impairment
Red impairment tags typically denote an emergency impairment, signaling an unplanned shutdown requiring immediate attention.
Which piece of information is NOT required on a standard impairment tag?
Answer: Estimated cost of the repair
The impairment tag documents operational details—who, what, where, and when—not financial information like repair costs.
If a fire were to occur during a system impairment, the building's first line of defense would be:
Answer: Trained fire watch personnel with portable extinguishers
When the automatic sprinkler system is impaired, fire watch personnel equipped with portable extinguishers serve as the primary initial response.