Workplace Communication & Documentation Flashcards
7 cards from real EPA 608 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Workplace Communication & Documentation flashcards as text
The leak rate trigger for commercial refrigeration appliances with 50+ lb charge is:
Answer: 20%
The 2016 rule set 20% for commercial refrigeration, 30% for industrial process, and 10% for comfort cooling.
Within what time frame must leaks generally be repaired after discovering the leak rate exceeds the threshold?
Answer: 30 days
Repairs are due within 30 days of discovery.
A technician repairs a leak. Verification tests should be done within how many days of the repair?
Answer: 30
Initial verification tests must be completed within 30 days of the repair attempt.
If a repair cannot be completed in 30 days, the owner must develop a retrofit or retirement plan within:
Answer: 30 days
The plan must be developed within 30 days and completed within one year.
What must the owner keep for each appliance with 50+ lb of charge besides refrigerant added?
Answer: Dates and results of leak inspections and repairs
Leak inspection and repair records are required.
A technician finds the leak rate was 25% on an industrial process unit. Is the 30% trigger met?
Answer: No, 25% is below the 30% threshold
Industrial process threshold is 30%, so 25% does not trigger repair.
Who bears the legal responsibility to keep leak repair records for an appliance?
Answer: The owner/operator
Owners/operators are responsible for leak repair compliance and records.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy