← All EPA 608 Flashcard Decks

Troubleshooting & Problem Solving Flashcards

7 cards from real EPA 608 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Troubleshooting & Problem Solving flashcards as text
  1. A system shows high suction pressure, low superheat, and a frosted suction line back to the compressor. What is the most likely cause?

    Answer: Overfeeding of the metering device or overcharge

    Excess liquid reaching the evaporator outlet gives low superheat and risks liquid floodback.

  2. A system has high superheat and low suction pressure. Which condition best explains this?

    Answer: Undercharge or a restriction starving the evaporator

    Too little refrigerant feeding the evaporator causes low pressure and the vapor to superheat excessively.

  3. A technician finds head pressure higher than the saturation pressure for the ambient temperature after the system has been off and stabilized. What is the likely cause?

    Answer: Non-condensable gases in the system

    Pressure higher than the saturation value for the ambient temperature points to air or other non-condensables.

  4. A technician finds a large temperature drop across the filter drier. What does this indicate?

    Answer: A restriction in the drier

    A noticeable temperature drop across a drier shows a partial restriction creating a pressure drop.

  5. The oil from a hermetic compressor smells acrid and is dark. What should the technician suspect?

    Answer: A motor burnout contaminating the system with acid

    Burnt-smelling dark oil indicates compressor motor burnout and acid contamination requiring cleanup.

  6. Which readings point to a dirty condenser coil?

    Answer: High head pressure, high discharge temperature, and reduced capacity

    Poor heat rejection raises condensing temperature and pressure, and reduces capacity.

  7. Moisture in a refrigeration system most often causes which problem at the metering device?

    Answer: Ice formation that restricts flow

    Water freezes at the metering device outlet and blocks refrigerant flow.

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. ecfr.gov — Exam format, test delivery, fees, passing score, retake policy, score release · verified Oct 2026
  2. epa.gov — Test delivery, eligibility, renewal, score validity · verified Oct 2026