Tools & Equipment Operation Flashcards
7 cards from real EPA 608 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Tools & Equipment Operation flashcards as text
At what pressure does a rupture disc on a low-pressure chiller typically release?
Answer: 15 psig
Low-pressure chiller rupture discs are rated at about 15 psig.
Why keep water flowing through a low-pressure chiller during recovery?
Answer: To prevent the tubes from freezing and rupturing
Falling refrigerant pressure lowers temperature, and stagnant water could freeze and damage tubes.
What evacuation level applies to low-pressure systems after recovery?
Answer: 25 mm Hg absolute
Low-pressure appliances must be evacuated to 25 mm Hg absolute.
Which refrigerant is commonly found in low-pressure chillers?
Answer: R-123
R-123 (and R-11 historically) are the typical low-pressure chiller refrigerants.
What is the push-pull method used for?
Answer: Recovering large amounts of liquid refrigerant quickly
Push-pull moves liquid from the system to a cylinder using a pressure differential.
What is the function of the filter-drier on recovery equipment?
Answer: Remove moisture, acid, and particulates
The filter-drier cleans the refrigerant and protects the recovery compressor.
Recovery equipment must be certified to which industry standard?
Answer: AHRI 740
AHRI 740 is the performance standard for recovery equipment certified by EPA-approved labs.