On a manifold gauge set, what does the blue compound gauge measure?
Answer: Low-side pressure and vacuum
The compound gauge reads both pressure (psig) and vacuum (inches Hg).
What is the yellow center hose on a manifold gauge set normally connected to?
Answer: A recovery machine, vacuum pump, or cylinder
The center hose is the service hose to the recovery unit, pump, or refrigerant cylinder.
Why use an electronic scale during recovery?
Answer: To monitor cylinder weight and avoid overfilling
A scale confirms the cylinder has not passed the 80% fill limit and tracks refrigerant recovered.
Which instrument is best for measuring a deep vacuum during evacuation?
Answer: Micron gauge
A micron gauge reads deep vacuum levels that a compound gauge cannot resolve.
What is a Schrader valve core removal tool used for?
Answer: Removing cores without losing refrigerant to speed evacuation and recovery
Removing cores increases flow area, speeding recovery and evacuation.
A pressure-temperature chart is used to find:
Answer: The saturation temperature for a given refrigerant pressure
The P-T chart relates a refrigerant's pressure to its saturation temperature.
What practice helps minimize refrigerant release when disconnecting hoses?
Answer: Using low-loss fittings or closing valves first
Low-loss fittings and closed valves keep refrigerant trapped in the hoses.