Strategic Planning & Implementation Flashcards
7 cards from real EPA 608 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Strategic Planning & Implementation flashcards as text
A facility with 100 lb of R-22 in a commercial refrigeration system finds a 25% annual leak rate. What threshold applies for required repairs?
Answer: 20%
Commercial refrigeration appliances with 50 or more pounds must be repaired when the leak rate exceeds 20%.
Within how many days must leaks be repaired once the leak rate threshold is exceeded for an appliance subject to leak repair?
Answer: 30 days
Owners generally must repair the leaks within 30 days of discovery.
What is the leak rate trigger for industrial process refrigeration?
Answer: 30%
Industrial process refrigeration has a 30% leak rate trigger.
What is the leak rate trigger for comfort cooling appliances with 50 or more pounds of ODS refrigerant?
Answer: 10%
Comfort cooling appliances are subject to repair at a leak rate above 10%.
After repairs, what must be done to confirm a leak has been fixed?
Answer: Perform initial and follow-up verification tests
Initial and follow-up verification tests must confirm the repairs worked.
How long must owners keep records of leak inspections and refrigerant additions?
Answer: 3 years
Records of service, leak inspections, and refrigerant added must be kept for 3 years.
An owner can seek an extension on leak repair if what condition exists?
Answer: Parts or industry shutdown prevents timely repair
Extensions apply for situations like needing parts or required industrial shutdowns, as documented.