Installation & Assembly Techniques Flashcards
7 cards from real EPA 608 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Installation & Assembly Techniques flashcards as text
Why is suction line insulation installed?
Answer: To prevent condensation and unwanted heat gain
Insulation limits sweating and keeps the vapor cold before it reaches the compressor.
What is the purpose of an oil trap at the base of a vertical suction riser?
Answer: To help return oil up to the compressor
Traps collect oil so vapor velocity can carry it up the riser back to the compressor.
Oversizing a suction line can cause:
Answer: Poor oil return due to low vapor velocity
Low velocity in a large line fails to push oil back to the compressor.
A liquid line filter drier should be installed:
Answer: In the liquid line with flow in the direction of the arrow
Drier flow direction must match the arrow so the desiccant filters properly.
Where is the thermostatic expansion valve sensing bulb typically mounted?
Answer: On the suction line near the evaporator outlet with good contact
The bulb must sense suction temperature at the evaporator outlet to control superheat.
Where is a sight glass normally installed?
Answer: In the liquid line, after the filter drier
Placed after the drier, it shows liquid flow condition and moisture indication.
Why should refrigerant lines be properly supported with hangers or isolators?
Answer: To prevent vibration fatigue and cracked tubing
Unsupported or rigid lines vibrate and fracture at joints, causing leaks.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy