  1. A 150-lb industrial process system had 60 lb added in 365 days. What is the leak rate?

    Answer: 40%

    60/150 = 40%, above the 30% trigger.

  2. A 90-lb commercial system receives 12 lb after 120 days. About what is the annualized leak rate?

    Answer: 40.6%

    12/90 × 365/120 × 100 ≈ 40.6%.

  3. When must a leak rate calculation be performed?

    Answer: Each time refrigerant is added to the appliance

    A calculation is required whenever refrigerant is added.

  4. Who is responsible for ensuring leak repair requirements are met?

    Answer: The appliance owner or operator

    Owners and operators bear responsibility for leak repair compliance.

  5. Leak repair requirements apply to appliances containing at least how much refrigerant?

    Answer: 50 lb

    The rules apply to appliances with 50 or more pounds of charge.

  6. A 120-lb comfort cooling system has a rolling leak rate of 8%. What is required?

    Answer: No mandatory repair since below 10%, but keep records

    8% is under the 10% trigger, so repair is not mandated, though records remain required.

  7. A 300-lb system had 3 lb added in 365 days. What is the leak rate?

    Answer: 1%

    3/300 = 1%.

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. ecfr.gov — Exam format, test delivery, fees, passing score, retake policy, score release · verified Oct 2026
  2. epa.gov — Test delivery, eligibility, renewal, score validity · verified Oct 2026