Data Analysis & Reporting Flashcards
7 cards from real EPA 608 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Data Analysis & Reporting flashcards as text
A 150-lb industrial process system had 60 lb added in 365 days. What is the leak rate?
Answer: 40%
60/150 = 40%, above the 30% trigger.
A 90-lb commercial system receives 12 lb after 120 days. About what is the annualized leak rate?
Answer: 40.6%
12/90 × 365/120 × 100 ≈ 40.6%.
When must a leak rate calculation be performed?
Answer: Each time refrigerant is added to the appliance
A calculation is required whenever refrigerant is added.
Who is responsible for ensuring leak repair requirements are met?
Answer: The appliance owner or operator
Owners and operators bear responsibility for leak repair compliance.
Leak repair requirements apply to appliances containing at least how much refrigerant?
Answer: 50 lb
The rules apply to appliances with 50 or more pounds of charge.
A 120-lb comfort cooling system has a rolling leak rate of 8%. What is required?
Answer: No mandatory repair since below 10%, but keep records
8% is under the 10% trigger, so repair is not mandated, though records remain required.
A 300-lb system had 3 lb added in 365 days. What is the leak rate?
Answer: 1%
3/300 = 1%.