Data Analysis & Reporting Flashcards
7 cards from real EPA 608 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Data Analysis & Reporting flashcards as text
A 200-lb comfort cooling system had 30 lb added over the past 365 days. What does the rolling method show?
Answer: 15%, exceeds trigger so repair is required
30/200 = 15%, above the 10% comfort cooling trigger.
What is the leak rate trigger for industrial process refrigeration?
Answer: 30%
Industrial process refrigeration triggers at 30%.
If repairs cannot bring the leak rate below the trigger, a retrofit or retirement plan must be completed within how long of the plan's development?
Answer: 1 year
The plan is developed within 30 days and completed within 1 year.
When must the initial verification test be performed?
Answer: Before the appliance is recharged, at the conclusion of repair work
The initial test confirms repairs worked before refrigerant is added back.
When is the follow-up verification test performed?
Answer: After the system has returned to normal operating conditions
The follow-up test confirms the repair holds under normal operating characteristics.
Which record is required when a 5–50 lb appliance is disposed of by a person who recovers its refrigerant?
Answer: Quantity of refrigerant recovered, retained for 3 years
Final disposal records must document the refrigerant recovered and be kept 3 years.
An 80-lb commercial refrigeration system receives 20 lb after 146 days. What is the annualized leak rate?
Answer: 62.5%
20/80 = 25%; × 365/146 (2.5) = 62.5%.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy