How long must leak repair and service records for an appliance holding 50+ lb of refrigerant be retained?
Answer: 3 years
EPA requires owners to keep these records for at least 3 years.
What is the leak rate trigger for commercial refrigeration appliances?
Answer: 20%
Commercial refrigeration appliances trigger repair requirements at a 20% annual leak rate.
A 100-lb system receives 15 lb after 73 days since the last addition. Using the annualizing method, what is the leak rate?
Answer: 75%
15/100 × 365/73 × 100 = 75%.
Which item must be recorded when refrigerant is added to an appliance with 50+ lb of charge?
Answer: Date and quantity of refrigerant added
Service records must show the date and amount of refrigerant added.
After a leak rate exceeds its trigger, within how many days must repairs be made?
Answer: 30 days
Leaks must be repaired within 30 days of discovering the rate exceeds the threshold.
The rolling average method for leak rate uses which data?
Answer: Refrigerant added in the past 365 days divided by full charge
It sums refrigerant added over the previous 365 days and divides by the full charge.
What is the leak rate trigger for comfort cooling appliances?
Answer: 10%
Comfort cooling appliances have the lowest threshold at 10%.