  1. Under NEC Article 230, what is the maximum number of service disconnects permitted for a single commercial occupancy?

    Answer: 6

    NEC 230.71 allows a maximum of six service disconnects for a single commercial occupancy grouped in one location.

  2. NEC 210.19(A) requires that branch circuit conductors have an ampacity of at least what percentage of the continuous load they serve?

    Answer: 125%

    Conductors must be sized at 125% of the continuous load to account for heat buildup under sustained operation.

  3. According to NEC 450.13, a dry-type transformer rated 112.5 kVA or less must have a minimum clearance of how many inches from combustible material?

    Answer: 12 inches

    NEC 450.13(A) requires at least 12 inches of separation between a dry-type transformer and combustible material unless the transformer is separated by a fire-resistant, heat-insulating barrier.

  4. NEC 700.12 requires emergency system sources to supply full load within how many seconds of normal power failure?

    Answer: 10 seconds

    Emergency systems must restore power within 10 seconds of normal source failure per NEC 700.12.

  5. Under NEC 404.2(C), a switch controlling a lighting outlet in a bathroom of a commercial occupancy must be located where?

    Answer: Inside the bathroom, away from the tub or shower

    NEC 404.2(C) permits switches inside bathrooms if they are not within reach of a tub or shower.

  6. NEC 517.13 requires that patient care areas in healthcare facilities have what special grounding provision for receptacles and fixed equipment?

    Answer: An insulated equipment grounding conductor in addition to the metallic raceway path

    NEC 517.13 mandates a redundant grounding path: both the metal raceway and an insulated EGC must be present to ensure continuity in patient care areas.

  7. According to NEC 225.30, a commercial building may have a maximum of how many feeder or branch circuit supplies from outside the building?

    Answer: One

    NEC 225.30 limits outside feeder or branch circuit supplies to one per building or structure, with specific listed exceptions.

  8. NEC 310.15(B) permits ambient temperature correction factors to be applied to conductor ampacity. What reference temperature is used for conductors rated 60°C through 90°C in standard NEC tables?

    Answer: 30°C

    The NEC ampacity tables are based on a 30°C (86°F) ambient temperature; correction factors must be applied for other ambient conditions.

  9. Under NEC 408.36, panelboards used as service equipment in commercial occupancies must be rated for use as service equipment, which requires what additional protection?

    Answer: A main overcurrent protective device or multiple main breakers not exceeding 6

    NEC 408.36 requires panelboards used as service equipment to have a main overcurrent device or not more than six circuit breakers to serve as the main disconnect.

  10. NEC 285.25 requires Type 1 SPDs installed on 120/240V single-phase services to be connected to which conductors?

    Answer: Each ungrounded conductor and the neutral

    Type 1 SPDs must connect between each ungrounded conductor and the neutral to provide proper surge protection across all legs.

  11. What does NEC 230.95 require on solidly grounded wye services of more than 150 volts to ground but not exceeding 600 volts phase-to-phase?

    Answer: Ground-fault protection of equipment (GFPE)

    NEC 230.95 mandates ground-fault protection of equipment for solidly grounded wye services over 150V to ground to prevent equipment damage from arcing ground faults.

  12. Per NEC 314.28(A)(1), straight pulls in pull boxes require the box length to be at least how many times the trade size of the largest raceway?

    Answer: 8 times

    For straight pulls, NEC 314.28(A)(1) requires the box length to be at least eight times the trade size of the largest raceway entering the box.

  13. NEC 501.15 governs conduit seals in Class I hazardous locations. Where must seals be installed relative to the boundary of the hazardous area?

    Answer: Within 18 inches of the hazardous area boundary

    Conduit seals must be placed within 18 inches of the hazardous area boundary to prevent ignitable vapors from traveling through the conduit system.

  14. According to NEC 250.66, the minimum size of the grounding electrode conductor for a service using 350 kcmil copper service conductors is:

    Answer: 2 AWG copper

    NEC Table 250.66 shows that 350 kcmil service conductors require a minimum 2 AWG copper grounding electrode conductor.

  15. NEC 410.116(B) requires fixtures installed in fire-rated ceilings to be marked with which designation?

    Answer: IC-rated

    Recessed luminaires installed in fire-rated assemblies must be IC-rated (Insulation Contact rated) and marked for installation in fire-rated ceilings.

  16. Under NEC 600.5, a sign or outline lighting system rated at 1200VA or less requires a branch circuit of at least what ampere rating?

    Answer: 20 amperes

    NEC 600.5(A) requires each commercial occupancy sign to be supplied by a dedicated branch circuit rated at least 20 amperes.

  17. Per NEC 358.20, what is the minimum trade size for Electrical Metallic Tubing (EMT) permitted in commercial wiring?

    Answer: 1/2 inch

    NEC 358.20 specifies that EMT is available in trade sizes 1/2 inch through 4 inches, making 1/2 inch the minimum permitted size.

  18. NEC 240.4(D) prohibits the use of overcurrent devices rated above 15 amperes to protect conductors of what size in commercial applications (copper)?

    Answer: 14 AWG

    NEC 240.4(D) specifies that 14 AWG copper conductors must not be protected by overcurrent devices rated more than 15 amperes.

  19. According to NEC 215.2(A)(1), the minimum ampacity for feeder conductors must be the greater of the computed load or what percentage of continuous loads plus 100% of noncontinuous loads?

    Answer: 125%

    Feeder conductors must be sized at 125% of the continuous load plus 100% of noncontinuous loads per NEC 215.2(A)(1).

  20. NEC 344.10 lists where Rigid Metal Conduit (RMC) is permitted. Which environment is specifically where RMC is permitted but IMC generally is NOT without additional protection?

    Answer: Concrete encasement in direct contact with the earth

    RMC's heavier wall provides corrosion resistance that makes it suitable for concrete encasement and direct burial without extra protection in most conditions.

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. iccsafe.org — Retake policy, renewal, score validity, score release, eligibility, passing score, exam format · verified Nov 2026
  2. shop.iccsafe.org — Fees, test dates · verified Nov 2026
NEC Compliance Flashcards — E2 Study Cards with Answers