Sizing and Protection of Motor Circuits Flashcards

21 cards from real E2 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 20 Sizing and Protection of Motor Circuits flashcards as text
  1. Per NEC 430.22, the minimum ampacity for branch circuit conductors supplying a single continuous-duty motor shall be what percentage of the motor's full-load current?

    Answer: 125% of FLA

    NEC 430.22 requires branch circuit conductor ampacity of at least 125% of the motor's FLA for continuous-duty applications.

  2. Which NEC table provides full-load current values for single-phase AC motors used for conductor and protection sizing?

    Answer: Table 430.248

    Table 430.248 lists FLA values for single-phase AC motors, which are used in place of nameplate values for conductor and overcurrent device sizing.

  3. A 5 HP, 230V, single-phase motor has a table FLA of 28A. What is the minimum required branch circuit conductor ampacity?

    Answer: 35A

    Minimum conductor ampacity = 125% × FLA = 1.25 × 28A = 35A per NEC 430.22.

  4. Per NEC 430.6(A)(1), which current value is used for sizing motor branch circuit conductors and short-circuit/ground-fault protective devices?

    Answer: Values from Tables 430.247 through 430.250

    NEC 430.6(A)(1) requires using table values from 430.247–430.250, not the motor nameplate, for conductor and short-circuit/ground-fault protection sizing.

  5. A 20 HP, 460V, 3-phase motor has a table FLA of 27A. What is the minimum branch circuit conductor ampacity required by NEC 430.22?

    Answer: 33.75A

    125% of 27A = 33.75A is the minimum conductor ampacity per NEC 430.22 for continuous-duty operation.

  6. Which NEC table provides full-load current values for 3-phase AC squirrel cage and synchronous motors?

    Answer: Table 430.250

    Table 430.250 provides FLA values for 3-phase AC motors, including squirrel cage and synchronous types, used for sizing conductors and overcurrent devices.

  7. Per NEC Table 430.22(E), motor branch circuit conductors for a 30-minute duty-rated motor must have an ampacity of at least what percentage of the motor's FLA?

    Answer: 150%

    NEC Table 430.22(E) requires 150% of FLA for branch circuit conductors supplying 30-minute and 60-minute duty-rated motors.

  8. Per NEC 430.32(A)(1), overload protection for a motor with a service factor of 1.15 or greater must be set to trip at no more than what percentage of the motor's FLA?

    Answer: 125% of FLA

    Motors with SF ≥ 1.15 or temperature rise ≤ 40°C require overload protection set to trip at no more than 125% of FLA per NEC 430.32(A)(1).

  9. For a motor with a service factor of 1.0 and a temperature rise exceeding 40°C, what is the maximum allowable overload trip setting per NEC 430.32(A)(1)?

    Answer: 115% of FLA

    Motors without SF ≥ 1.15 or temperature rise ≤ 40°C are limited to an overload trip setting of no more than 115% of FLA.

  10. A 460V, 3-phase motor has a nameplate FLA of 22A and a service factor of 1.15. What is the maximum overload relay trip setting per NEC 430.32(A)(1)?

    Answer: 27.5A

    With SF ≥ 1.15, maximum overload setting = 125% of nameplate FLA = 1.25 × 22A = 27.5A.

  11. Per NEC 430.32(C), if the standard overload setting is insufficient to start or carry the load for a motor with SF ≥ 1.15, the maximum allowable trip setting may be increased to:

    Answer: 140% of FLA

    NEC 430.32(C) permits the trip setting to be increased up to 140% of FLA for motors with SF ≥ 1.15 when the standard setting cannot carry the load.

  12. Per NEC 430.37, how many overload sensing elements are required for a 3-wire, 3-phase motor with no neutral conductor?

    Answer: 3 elements

    NEC 430.37 requires one overload sensing element in each of the three ungrounded phase conductors for a 3-wire, 3-phase motor.

  13. Per NEC 430.32(B), a motor with a nameplate marked 'thermally protected' may use the built-in thermal protector to serve as the overload protection, provided the protector is approved for use with the motor and will:

    Answer: Prevent dangerous overheating of the motor

    NEC 430.32(B) allows built-in thermal protectors as overload protection when approved for use with the specific motor and capable of preventing dangerous overheating.

  14. Per NEC 430.43, where the automatic restarting of a motor after an overload trip could be hazardous to personnel, which type of overload device is prohibited?

    Answer: Automatic reset overload relay

    Automatic reset overload relays are prohibited where automatic restarting after a trip would endanger personnel, as no human action is required to restart the motor.

  15. Per NEC Table 430.52, the maximum rating of an inverse time circuit breaker for a Design B, squirrel cage motor branch circuit is:

    Answer: 250% of FLA

    Table 430.52 allows a maximum inverse time circuit breaker rating of 250% of the motor's FLA for Design B squirrel cage motors.

  16. Per NEC Table 430.52, the maximum rating for a non-time-delay fuse used for branch-circuit short-circuit protection of a Design B squirrel cage motor is:

    Answer: 300% of FLA

    Table 430.52 permits non-time-delay fuses rated up to 300% of the motor's FLA for branch-circuit short-circuit and ground-fault protection.

  17. Per NEC Table 430.52, the maximum dual element (time-delay) fuse rating for a Design B squirrel cage motor is:

    Answer: 175% of FLA

    Dual element time-delay fuses are limited to 175% of the motor FLA for Design B motors under Table 430.52.

  18. Per NEC 430.52(C)(2), if the maximum standard inverse time breaker size cannot carry the motor's starting current, the breaker rating may be increased to a maximum of:

    Answer: 400% of FLA

    NEC 430.52(C)(2) allows the inverse time breaker to be increased to a maximum of 400% of FLA when the standard 250% cannot handle motor starting current.

  19. Per NEC 430.110(A), the ampere rating of the motor circuit disconnecting means must be at least what percentage of the motor's full-load current rating?

    Answer: 115%

    NEC 430.110(A) requires the motor disconnecting means to have an ampere rating of at least 115% of the motor's full-load current rating.

  20. Per NEC 430.52(C)(1), when the maximum calculated branch-circuit protective device rating does not correspond to a standard fuse or breaker size, the installer shall use:

    Answer: The next higher standard rating

    NEC 430.52(C)(1) permits rounding up to the next higher standard fuse or breaker size when the calculated maximum value is not a standard rating.

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. iccsafe.org — Retake policy, renewal, score validity, score release, eligibility, passing score, exam format · verified Nov 2026
  2. shop.iccsafe.org — Fees, test dates · verified Nov 2026