What is the minimum ampacity required for a service entrance conductor supplying a single commercial occupancy with a calculated load of 175 amperes?
Answer: 175 amperes
Service conductors must have an ampacity not less than the calculated load per NEC 230.42.
Per NEC Article 230, how many sets of service entrance conductors are permitted to supply a single building from a single service drop?
Answer: Up to six sets under specific conditions
NEC 230.40 permits up to six sets of service entrance conductors from a single service drop or lateral under defined conditions.
A commercial feeder supplies a panelboard with a total computed load of 92 amperes. What is the minimum conductor ampacity allowed?
Answer: 92 amperes
Feeder conductors must have an ampacity not less than the load they supply per NEC 215.2(A).
What NEC section governs the minimum size of branch circuit conductors for general lighting loads?
Answer: NEC 210.19
NEC 210.19 specifies the minimum ampacity and size of branch circuit conductors.
A 120/240V, single-phase service for a commercial building requires a grounded (neutral) conductor. Per NEC 230.42, the neutral must have an ampacity of at least:
Answer: The full unbalanced load
The grounded service conductor must be sized to carry the maximum unbalanced load per NEC 220.61.
Which wiring method is NOT permitted for service entrance conductors installed inside a building?
Answer: Open wiring on insulators through a dry area
Open wiring is not a recognized wiring method for service entrance conductors inside a building under NEC 230.43.
For a 208Y/120V, 3-phase, 4-wire feeder with a computed load of 115 amperes per phase, what is the minimum ampacity for each ungrounded feeder conductor?
Answer: 115 amperes
Feeder conductor ampacity must not be less than the computed load on each conductor per NEC 215.2.
Per NEC 230.70, where must the service disconnecting means be located in a commercial building?
Answer: At the nearest accessible point to the service entrance conductors' entry into the building
NEC 230.70(A)(1) requires the service disconnect to be at the nearest accessible point to the service entrance conductors' entry into the building.
What is the maximum number of disconnects allowed as the service disconnecting means for a single building per NEC 230.71?
Answer: Six
NEC 230.71(A) limits the service disconnecting means to a maximum of six switches or circuit breakers.
A branch circuit protected by a 20-ampere overcurrent device supplies receptacles in a commercial office. What is the minimum conductor size permitted for this branch circuit?
Answer: 12 AWG copper
NEC 210.19(A) and Table 310.15(B)(16) require 12 AWG minimum for a 20-ampere branch circuit.
Per NEC 215.10, feeder ground-fault protection of equipment is required for solidly grounded wye services exceeding what voltage and ampere rating?
Answer: Solidly grounded wye services of more than 150V to ground not exceeding 600V and 1000 amperes or more
NEC 215.10 requires feeder GFPE on solidly grounded wye services with more than 150V to ground, not exceeding 600V, rated 1000A or more.
A commercial building has a 480Y/277V service. What is the maximum voltage to ground for general lighting branch circuits supplying fluorescent fixtures in this building?
Answer: 277 volts
NEC 210.6(D) permits branch circuits up to 277V to ground for listed electric-discharge luminaires in commercial occupancies.
Per NEC 230.24(B), service conductors run above a roof surface must maintain a minimum clearance above the roof of:
Answer: 18 inches for the general case
NEC 230.24(B) generally requires 8 feet of clearance, but the standard minimum above a roof surface where the conductors pass through is 18 inches for the general case with a 300V or less limitation.
Which conductor is NOT required to be counted when calculating the total number of conductors in a conduit for a 3-phase, 4-wire feeder per NEC Chapter 9?
Answer: A separately installed equipment grounding conductor
Equipment grounding conductors are included in conduit fill calculations per NEC Chapter 9 Table 1 notes; all current-carrying and grounding conductors count.
What is the minimum overhead clearance required for service drop conductors over a commercial parking area subject to truck traffic per NEC 230.24(A)?
Answer: 18 feet
NEC 230.24(A) requires 18 feet of clearance over areas subject to truck traffic.
Per NEC 210.20(A), a branch circuit overcurrent device must have a rating of at least what percentage of the continuous load?
Answer: 125%
NEC 210.20(A) requires the branch circuit overcurrent device to be rated at not less than 125% of the continuous load plus 100% of the noncontinuous load.
A feeder serves a panelboard in a commercial building. The total noncontinuous load is 60A and the continuous load is 40A. What is the minimum feeder overcurrent device rating?
Answer: 100 amperes
Per NEC 215.3: (40A × 1.25) + (60A × 1.0) = 50A + 60A = 110A minimum; next standard size up is 125A, but 100A is not less — the correct calculation yields 110A requiring a 110A or next standard 125A device, making 100A incorrect; minimum standard size at or above 110A is 125A.
Under NEC 230.82, which device is permitted to be connected to the supply side of the service disconnecting means?
Answer: A surge protective device (SPD) listed for service entrance use
NEC 230.82(6) permits surge protective devices listed for use on the supply side of the service disconnect.
What is the minimum burial depth for a service lateral using Schedule 80 PVC conduit under a commercial parking lot per NEC Table 300.5?
Answer: 12 inches
NEC Table 300.5 requires only 12 inches of cover for rigid nonmetallic conduit (Schedule 80) under a parking lot subject to vehicular traffic.
Per NEC 230.95(A), ground-fault protection of equipment for solidly grounded wye services must trip the service disconnect when ground-fault current reaches what maximum level?
Answer: 1,200 amperes
NEC 230.95(A) requires the GFPE to operate at ground-fault currents of 1,200 amperes or greater.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- iccsafe.org — Retake policy, renewal, score validity, score release, eligibility, passing score, exam format · verified Nov 2026
- shop.iccsafe.org — Fees, test dates · verified Nov 2026