Motors and Transformers Flashcards
7 cards from real E2 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Motors and Transformers flashcards as text
Per NEC 450.21, a dry-type transformer rated 1000V or less installed indoors must be rated at what minimum temperature class?
Answer: 130°C (Class B)
NEC 450.21(A) requires dry-type transformers rated 1000V or less installed indoors to have a 130°C or higher insulation temperature rating.
A variable frequency drive (VFD) is used to control a 3-phase motor. The VFD's input current rating should be based on:
Answer: The VFD nameplate input ampere rating
NEC 430.122 requires VFD branch-circuit conductors to be sized at 125% of the VFD's nameplate input current, not the motor FLC.
What NEC section addresses the grounding of a separately derived transformer system with a primary voltage over 1000V?
Answer: NEC 250.30
NEC 250.30 covers grounding of separately derived AC systems, including transformer secondaries at any voltage.
When sizing conductors for a feeder supplying several motors, NEC 430.24 requires the feeder ampacity to equal the largest motor FLC multiplied by 125% plus:
Answer: The sum of the remaining motor FLCs at 100%
NEC 430.24 adds 125% of the largest motor FLC to the sum of all other motor full-load currents at 100%.
An autotransformer used for reduced-voltage motor starting must have its common winding connected to:
Answer: Both line and load conductors
An autotransformer has a single continuous winding where the common winding section is shared between the primary and secondary circuits.
Per NEC 430.53, multiple motors may be connected to one branch circuit without individual overload protection only if all motors are rated:
Answer: Less than 1 HP and FLC does not exceed 6 A
NEC 430.53(A) permits multiple motors on one branch circuit if each motor is 1 HP or less and FLC does not exceed 6 A.
A transformer secondary conductor run in a separate raceway from the transformer to the first overcurrent device must be protected at its ampacity unless:
Answer: It meets the physical protection requirements of NEC 240.21(C)
NEC 240.21(C) provides tap rules allowing transformer secondary conductors to run without overcurrent protection at the transformer if specific length, termination, and conductor sizing conditions are met.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- iccsafe.org — Retake policy, renewal, score validity, score release, eligibility, passing score, exam format · verified Nov 2026
- shop.iccsafe.org — Fees, test dates · verified Nov 2026