Mixed Deck — All E2 Topics Flashcards
100 cards from real E2 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 20 Mixed Deck — All E2 Topics flashcards as text
A transformer nameplate lists an impedance of 5.75%. This value is primarily used to calculate:
Answer: Available fault current
Transformer impedance (%Z) is the key parameter for calculating available short-circuit current on the secondary side.
Per NEC 312.11, when shall a wiring enclosure (cabinet or cutout box) be secured to the wall or other supporting surface?
Answer: It shall be securely fastened in place
NEC 312.11 requires that all cabinets, cutout boxes, and meter socket enclosures be securely fastened in place.
A run of rigid PVC conduit passes through a building expansion joint. The inspector should verify the presence of:
Answer: An expansion coupling listed for the purpose
NEC 352.44 requires an expansion fitting listed for PVC where the conduit crosses a structural expansion joint.
When sizing conductors for a feeder supplying several motors, NEC 430.24 requires the feeder ampacity to equal the largest motor FLC multiplied by 125% plus:
Answer: The sum of the remaining motor FLCs at 100%
NEC 430.24 adds 125% of the largest motor FLC to the sum of all other motor full-load currents at 100%.
In a Class I, Zone 0 location per NEC Article 505, flammable concentrations of gases are present:
Answer: Continuously or for long periods under normal conditions
Zone 0 is the most hazardous classification under the Zone system, where flammable concentrations are present continuously or for long periods.
NEC 501.15 governs conduit seals in Class I hazardous locations. Where must seals be installed relative to the boundary of the hazardous area?
Answer: Within 18 inches of the hazardous area boundary
Conduit seals must be placed within 18 inches of the hazardous area boundary to prevent ignitable vapors from traveling through the conduit system.
Which NEC section governs the illumination requirements for working spaces about electrical equipment?
Answer: NEC 110.26(D)
NEC 110.26(D) requires adequate illumination for all working spaces about electrical equipment.
An inspector is reviewing plans for a restaurant kitchen and notices that the equipment grounding conductors for all circuits are shown as the same size. What potential issue should be investigated?
Answer: NEC 250.122 requires EGCs to be sized based on the rating of the overcurrent device protecting each circuit
NEC 250.122 requires equipment grounding conductors to be sized based on the ampere rating of the overcurrent protective device in the circuit, so larger circuits need larger EGCs.
During an inspection, you find a disconnect switch installed higher than 6 feet 7 inches above the floor. What should you do?
Answer: Require the switch to be relocated within the acceptable height range
The National Electrical Code (NEC) specifies maximum heights for disconnect switches and other control devices to ensure they are readily accessible and operable for all personnel, including those with disabilities. A disconnect switch installed higher than 6 feet 7 inches (2.0 m) violates NEC 404.8(A) for switches and circuit breakers. This non-compliance must be corrected to ensure safe and accessible operation of the electrical system.
During an E2 inspection, an inspector finds that a 480V motor control center (MCC) has been relocated 18 inches closer to a wall, reducing the rear working space. The original installation required rear access. This violates:
Answer: NEC 110.26(A)(2) which requires 30 inches of working space when rear access to live parts is needed
NEC 110.26(A)(2) requires the same working space at the rear of equipment where rear access is necessary to work on live or energized parts.
Which wiring method is NOT permitted for service entrance conductors installed inside a building?
Answer: Open wiring on insulators through a dry area
Open wiring is not a recognized wiring method for service entrance conductors inside a building under NEC 230.43.
An E2 inspector finds that a commercial building's electrical service equipment has no field-applied arc flash label. Under NFPA 70E 130.5(H), the owner is required to:
Answer: Perform an arc flash hazard analysis and label the equipment before work begins
NFPA 70E 130.5(H) requires equipment to be field-marked with arc flash hazard information based on an engineering study before energized work is performed.
According to NEC Article 700, what is the maximum time permitted for an emergency system to automatically connect to its power source after an interruption of the normal supply?
Answer: 10 seconds
NEC 700.12 states that emergency systems must have automatic transfer equipment that restores power within 10 seconds of a normal power failure. This rapid transfer is critical for life safety systems like egress lighting and fire alarms.
During a plan review, an inspector sees that the one-line diagram shows a 2000A service with a single 2000A disconnect. The building also has an emergency generator. Which NEC section governs the number and grouping of service disconnects?
Answer: NEC 230.71, which limits service disconnecting means to a maximum of six disconnects
NEC 230.71 permits a maximum of six disconnects for a service, and all disconnects must be grouped together.
A commercial plan set shows a 480V, 3-phase panel with a 400A main breaker but the service conductors are sized for only 350A. What is the correct inspector action?
Answer: Reject the plans and require conductors sized to at least 400A or a smaller main breaker
NEC 230.90 requires the service overcurrent device to not exceed the ampacity of the service conductors it protects.
A commercial inspector finds 12 THHN conductors in a single conduit run in an ambient of 30°C. What combined adjustment and correction factor applies to the 90°C column ampacity?
Answer: 0.50 × 1.00 = 0.50
For 10-20 conductors, Table 310.15(C)(1) gives 0.50; at 30°C ambient, the 90°C correction factor is 1.00, so the combined factor is 0.50 × 1.00 = 0.50.
NEC 110.26(E) requires that the entrance to working spaces about electrical equipment be kept clear of obstructions. What specific door requirement is noted for large installations?
Answer: Doors must open in the direction of egress and be equipped with panic hardware
NEC 110.26(C)(1) requires that personnel doors for rooms with large electrical equipment must open in the direction of egress and be equipped with panic bars or other listed hardware.
Where must the equipment grounding conductor in a patient care area be insulated?
Answer: Throughout its entire length from panel to receptacle
NEC 517.13(B) requires the equipment grounding conductor to be insulated throughout its entire length in patient care branch circuit wiring.
NEC 230.6 states that service conductors are considered 'outside a building' when they are installed:
Answer: Under at least 2 inches of concrete beneath a building, or within a building in a raceway enclosed by 2 inches of concrete
NEC 230.6 allows conductors installed under at least 2 inches of concrete beneath a building or enclosed by 2 inches of concrete within a building to be considered as outside the building.
Pipes, ducts, or equipment foreign to electrical installations are permitted in dedicated electrical space under which condition?
Answer: Never — NEC strictly prohibits all foreign systems
NEC 110.26(F)(1)(b) states that the dedicated space shall not be used for piping, ducts, leak protection apparatus, or any equipment foreign to the electrical installation.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy