What is the total calculated load for 50 duplex receptacle outlets in a commercial space before applying demand factors?
Answer: 9,000 VA
Each duplex outlet counts as one yoke at 180 VA, so 50 × 180 VA = 9,000 VA per NEC 220.14(I).
Under what condition does NEC 220.87 permit the optional method for determining commercial service capacity?
Answer: Existing service or feeder capacity evaluation using measured demand data
NEC 220.87 is specifically intended for evaluating existing service or feeder capacity using actual demand measurements over time.
A commercial service calculation yields 285,000 VA on a 120/208V, 3-phase system. What minimum service ampacity is required?
Answer: 800A
285,000 VA ÷ (208V × 1.732) ≈ 791A, requiring the next standard size of 800A.
What must an electrical inspector verify about continuous loads in a submitted commercial service calculation?
Answer: Continuous loads are included at 125% of full-load current per NEC 215.2
NEC 215.2(A)(1) requires continuous loads to be calculated at 125% of their full-load current when sizing feeders and services.
When sizing the neutral conductor for a commercial service, which load type carries no neutral current and does not require neutral conductor capacity?
Answer: Balanced 3-phase motor loads
Balanced 3-phase loads such as motors produce no neutral current because the phases cancel each other out.
A commercial warehouse has 200,000 VA of general lighting load. What is the demand load after applying NEC Table 220.42 factors for warehouses?
Answer: 125,000 VA
For 'all other' occupancies: first 50,000 VA × 100% = 50,000 VA, plus 150,000 VA × 50% = 75,000 VA, totaling 125,000 VA.
Per NEC Table 220.55, what is the maximum demand used when a commercial establishment has a single household cooking unit rated 12 kW?
Answer: 8 kW
NEC Table 220.55 permits a maximum demand of 8 kW for a single range rated 12 kW or less.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- iccsafe.org — Retake policy, renewal, score validity, score release, eligibility, passing score, exam format · verified Nov 2026
- shop.iccsafe.org — Fees, test dates · verified Nov 2026