← All E2 Flashcard Decks

Commercial Service Load Calculations Flashcards

7 cards from real E2 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Commercial Service Load Calculations flashcards as text
  1. What is the total calculated load for 50 duplex receptacle outlets in a commercial space before applying demand factors?

    Answer: 9,000 VA

    Each duplex outlet counts as one yoke at 180 VA, so 50 × 180 VA = 9,000 VA per NEC 220.14(I).

  2. Under what condition does NEC 220.87 permit the optional method for determining commercial service capacity?

    Answer: Existing service or feeder capacity evaluation using measured demand data

    NEC 220.87 is specifically intended for evaluating existing service or feeder capacity using actual demand measurements over time.

  3. A commercial service calculation yields 285,000 VA on a 120/208V, 3-phase system. What minimum service ampacity is required?

    Answer: 800A

    285,000 VA ÷ (208V × 1.732) ≈ 791A, requiring the next standard size of 800A.

  4. What must an electrical inspector verify about continuous loads in a submitted commercial service calculation?

    Answer: Continuous loads are included at 125% of full-load current per NEC 215.2

    NEC 215.2(A)(1) requires continuous loads to be calculated at 125% of their full-load current when sizing feeders and services.

  5. When sizing the neutral conductor for a commercial service, which load type carries no neutral current and does not require neutral conductor capacity?

    Answer: Balanced 3-phase motor loads

    Balanced 3-phase loads such as motors produce no neutral current because the phases cancel each other out.

  6. A commercial warehouse has 200,000 VA of general lighting load. What is the demand load after applying NEC Table 220.42 factors for warehouses?

    Answer: 125,000 VA

    For 'all other' occupancies: first 50,000 VA × 100% = 50,000 VA, plus 150,000 VA × 50% = 75,000 VA, totaling 125,000 VA.

  7. Per NEC Table 220.55, what is the maximum demand used when a commercial establishment has a single household cooking unit rated 12 kW?

    Answer: 8 kW

    NEC Table 220.55 permits a maximum demand of 8 kW for a single range rated 12 kW or less.