Commercial Service Load Calculations Flashcards
7 cards from real E2 practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Commercial Service Load Calculations flashcards as text
What is the minimum show window lighting load per linear foot required in commercial load calculations per NEC 220.14(G)?
Answer: 200 VA
NEC 220.14(G) requires a minimum of 200 VA per linear foot of show window for load calculations.
When a commercial building has both electric heating and air conditioning as non-coincident loads, what does NEC 220.60 permit?
Answer: Use only the larger load and omit the smaller
NEC 220.60 allows the smaller of two non-coincident loads to be omitted because both will not operate simultaneously.
For commercial service calculations involving motor loads, what percentage of the largest motor's full-load current must be added to the total per NEC 220.50?
Answer: 25%
NEC 220.50 requires 25% of the largest motor's full-load current to be added to feeder and service calculations.
Per NEC Table 220.56, what demand factor applies to commercial kitchen equipment when there are only 2 cooking units?
Answer: 100%
NEC Table 220.56 requires 100% demand factor when a commercial kitchen has only 1 or 2 units of cooking equipment.
What minimum load must be calculated for each required commercial sign or outline lighting outlet per NEC 220.14(F)?
Answer: 1,200 VA
NEC 220.14(F) mandates a minimum 1,200 VA for each required sign or outline lighting outlet in commercial occupancies.
An inspector notices a designer used 1,500 VA per circuit for receptacles in a commercial tenant space. What is the correct NEC method?
Answer: 180 VA per individual receptacle outlet on the yoke
In commercial (non-dwelling) spaces, receptacles are calculated at 180 VA per outlet per NEC 220.14(I), not per circuit.
A commercial HVAC system has a 40-ampere, 208V, 3-phase compressor motor. How is this load properly treated in a service calculation?
Answer: Motor load added at 100% FLC with 25% of largest motor added separately
HVAC compressor motors are included at 100% FLC in the total, and per NEC 220.50 an additional 25% of the largest motor is added.
Written and edited by Nathan Beja, founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- iccsafe.org — Retake policy, renewal, score validity, score release, eligibility, passing score, exam format · verified Nov 2026
- shop.iccsafe.org — Fees, test dates · verified Nov 2026