E2 Cheat Sheet 2026
The 30 highest-yield E2 facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.
80 questions
210 min time limit
75.00% to pass
- Which branch of the essential electrical system in a hospital must power the fire alarm system? → Life safety branch
- Which of the following circuits requires GFCI protection in a commercial building? → Receptacles in restrooms
- An Optional Standby System under NEC Article 702 is intended to protect: → Business or property from inconvenience or financial loss
- Which of the following is a standard ampere rating for overcurrent devices per NEC 240.6(A)? → 45 amperes
- Equipment grounding conductors installed in conduit must be sized based on which NEC table? → Table 250.122
- Under NEC Article 504, an intrinsically safe system is one in which any spark or thermal effect is incapable of causing ignition under which condition? → Both normal and abnormal conditions as specified
- In spray application areas covered by NEC Article 516, the zone immediately surrounding open containers of flammable liquids is classified as: → Class I, Division 2 within 3 feet
- Under the NEC, a motor controller must be capable of interrupting the stalled-rotor current of the motor it controls. This rating is known as the: → Locked rotor current (LRC)
- Which of the following wiring methods is permitted by the NEC to be installed in direct contact with the earth (direct burial) when made of galvanized steel? → Rigid Metal Conduit (RMC)
- If ten 12 AWG THHN copper current-carrying conductors are installed in a single conduit, what adjustment factor must be applied to their ampacity? → 50%
- Which NEC section governs the illumination requirements for working spaces about electrical equipment? → NEC 110.26(D)
- In a separately derived system from a transformer, where is the system bonding jumper installed? → At the source of the separately derived system or at the first disconnect
- What is the minimum headroom in a high-voltage (over 1000V) working space per NEC 110.34(E)? → 7 feet
- Under NEC Article 520 governing theaters, the dimmer system conductors in the stage switchboard area must be protected against: → Both overcurrent and short circuit using listed theatrical equipment
- When inspecting a variable frequency drive (VFD) installation, which conductor issue is most critical to verify? → Conductor ampacity derating for harmonic heating
- What is the minimum bend radius for a 1-inch EMT conduit field bend to the inside of the bend? → 4 inches
- What is the primary purpose of reviewing electrical blueprints during plan review? → To verify compliance with applicable codes and standards
- What is the maximum distance allowed between a motor disconnect and the motor it serves, per NEC 430.102(B)? → The disconnect must be within sight of the motor
- NEC 210.8(B) requires GFCI protection for 125-volt through 250-volt receptacles in commercial kitchens located within how many feet of a sink? → 6 feet
- Under NEC Article 330, Metal-Clad (MC) cable installed exposed in a commercial building must be supported at intervals not exceeding: → 6 feet
- Per NEC Table 220.55, what is the maximum demand used when a commercial establishment has a single household cooking unit rated 12 kW? → 8 kW
- Under NEC 240.4(D), what is the maximum overcurrent protection for 10 AWG copper conductors? → 30 amperes
- NEC 230.70 requires the service disconnecting means to be installed: → Outside the building or inside nearest the point of entrance of service conductors
- When parallel conductors are used, how must equipment grounding conductors be sized? → Each parallel set must contain a full-size EGC based on the overcurrent device
- An emergency generator's fuel supply must be adequate to operate the system for a minimum of: → 4 hours at full load
- A 100 HP, 460V, 3-phase motor has a FLC of 124 A per Table 430.250. Using dual-element time-delay fuses, what is the maximum fuse rating per NEC Table 430.52? → 225 A
- Per NEC Table 430.52, the maximum rating of an inverse time circuit breaker for a Design B, squirrel cage motor branch circuit is: → 250% of FLA
- A portable generator used as an Optional Standby source must be connected using a listed transfer device. The main reason is to prevent: → Backfeed to the utility system endangering line workers
- A retail mall tenant has 500 linear feet of show window frontage. What minimum load must be added to the service calculation per NEC 220.14(G)? → 100,000 VA
- Per NEC 450.14, transformers must be provided with a means to disconnect all ungrounded conductors. For a transformer rated over 600V, this disconnect must be: → Lockable in the open position if not within sight