E2 Cheat Sheet 2026

The 30 highest-yield E2 facts, distilled from real exam questions. Print it, save it as a PDF, or study it here โ€” free, no sign-up.

E2 exam key facts

  • The ICC E2 Commercial Electrical Inspector exam has 80 multiple-choice questions and is open book. Source
  • ICC National Certification exams, including the E2 Commercial Electrical Inspector exam, have a passing scaled score of 75. Source
  • The ICC Commercial Electrical Inspector exam (E2) costs $320 per exam purchase. Source
  • ICC National Certification exams, including the E2 Commercial Electrical Inspector exam, allow six exam attempts within a six-month period. Source
  • ICC certifications, including the E2 Commercial Electrical Inspector certification, are valid for three years. Source
Start the Timed E2 Mock Exam โ†’
80 questions
210 min time limit
75.00% to pass
  1. Which branch of the essential electrical system in a hospital must power the fire alarm system? โ†’ Life safety branch
  2. Which of the following circuits requires GFCI protection in a commercial building? โ†’ Receptacles in restrooms
  3. An Optional Standby System under NEC Article 702 is intended to protect: โ†’ Business or property from inconvenience or financial loss
  4. Which of the following is a standard ampere rating for overcurrent devices per NEC 240.6(A)? โ†’ 45 amperes
  5. Equipment grounding conductors installed in conduit must be sized based on which NEC table? โ†’ Table 250.122
  6. Under NEC Article 504, an intrinsically safe system is one in which any spark or thermal effect is incapable of causing ignition under which condition? โ†’ Both normal and abnormal conditions as specified
  7. In spray application areas covered by NEC Article 516, the zone immediately surrounding open containers of flammable liquids is classified as: โ†’ Class I, Division 2 within 3 feet
  8. Under the NEC, a motor controller must be capable of interrupting the stalled-rotor current of the motor it controls. This rating is known as the: โ†’ Locked rotor current (LRC)
  9. Which of the following wiring methods is permitted by the NEC to be installed in direct contact with the earth (direct burial) when made of galvanized steel? โ†’ Rigid Metal Conduit (RMC)
  10. If ten 12 AWG THHN copper current-carrying conductors are installed in a single conduit, what adjustment factor must be applied to their ampacity? โ†’ 50%
  11. Which NEC section governs the illumination requirements for working spaces about electrical equipment? โ†’ NEC 110.26(D)
  12. Under NEC Article 520 governing theaters, the dimmer system conductors in the stage switchboard area must be protected against: โ†’ Both overcurrent and short circuit using listed theatrical equipment
  13. When inspecting a variable frequency drive (VFD) installation, which conductor issue is most critical to verify? โ†’ Conductor ampacity derating for harmonic heating
  14. What is the minimum bend radius for a 1-inch EMT conduit field bend to the inside of the bend? โ†’ 4 inches
  15. What is the primary purpose of reviewing electrical blueprints during plan review? โ†’ To verify compliance with applicable codes and standards
  16. What is the maximum distance allowed between a motor disconnect and the motor it serves, per NEC 430.102(B)? โ†’ The disconnect must be within sight of the motor
  17. Under NEC Article 330, Metal-Clad (MC) cable installed exposed in a commercial building must be supported at intervals not exceeding: โ†’ 6 feet
  18. Per NEC Table 220.55, what is the maximum demand used when a commercial establishment has a single household cooking unit rated 12 kW? โ†’ 8 kW
  19. Under NEC 240.4(D), what is the maximum overcurrent protection for 10 AWG copper conductors? โ†’ 30 amperes
  20. NEC 230.70 requires the service disconnecting means to be installed: โ†’ Outside the building or inside nearest the point of entrance of service conductors
  21. An emergency generator's fuel supply must be adequate to operate the system for a minimum of: โ†’ 4 hours at full load
  22. A 100 HP, 460V, 3-phase motor has a FLC of 124 A per Table 430.250. Using dual-element time-delay fuses, what is the maximum fuse rating per NEC Table 430.52? โ†’ 225 A
  23. Per NEC Table 430.52, the maximum rating of an inverse time circuit breaker for a Design B, squirrel cage motor branch circuit is: โ†’ 250% of FLA
  24. A portable generator used as an Optional Standby source must be connected using a listed transfer device. The main reason is to prevent: โ†’ Backfeed to the utility system endangering line workers
  25. A retail mall tenant has 500 linear feet of show window frontage. What minimum load must be added to the service calculation per NEC 220.14(G)? โ†’ 100,000 VA
  26. Per NEC 450.14, transformers must be provided with a means to disconnect all ungrounded conductors. For a transformer rated over 600V, this disconnect must be: โ†’ Lockable in the open position if not within sight
  27. Under NEC 600.5, a sign or outline lighting system rated at 1200VA or less requires a branch circuit of at least what ampere rating? โ†’ 20 amperes
  28. Under NEC 250.104, metal water piping systems in a commercial building must be bonded to which of the following? โ†’ Service equipment enclosure, grounded conductor, or grounding electrode conductor
  29. Which NEC provision allows the working space in front of electrical equipment to serve as egress, and what is the key requirement? โ†’ NEC 110.26(C)(2) โ€” the path must not pass through the working space of other equipment
  30. Under NEC 240.81, when a single-throw circuit breaker is used as a disconnecting means, the 'ON' position of the operating handle shall be in what direction? โ†’ Upward

What Practice Test Geeks adds beyond an AI chat for E2

An AI chatbot can quiz you, but it can't reproduce the exam conditions or keep your record. Here you get:

  • A timed, full-length E2 mock exam โ€” 80 questions in 210 minutes with a 75% pass mark, modeled on the official exam's question count and time limit, followed by a score report broken down by exam domain.
  • A fixed E2 question bank: the same test every attempt, so your score is comparable from one try to the next instead of changing with every regenerated quiz.
  • Progress saved on your device: completed tests, scores and missed questions stay in My Progress, so you can retake only what you got wrong.
  • E2 flashcards built from the same question bank.
  • Free E2 practice tests with the correct answer shown after each question.
Start the Timed E2 Mock Exam โ†’
Was this helpful?

Written and edited by , founder of Practice Test Geeks, with AI assistance. Exam facts are checked against the official sources linked below. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. iccsafe.org โ€” Retake policy, renewal, score validity, score release, eligibility, passing score, exam format ยท verified Nov 2026
  2. shop.iccsafe.org โ€” Fees, test dates ยท verified Nov 2026