  1. What is the recommended minimum flow rate per ton of capacity for a residential closed-loop geothermal system using water as the heat transfer fluid?

    Answer: 1.5–3.0 GPM per ton

    IGSHPA and equipment manufacturers recommend 1.5–3.0 GPM per ton to ensure adequate heat transfer and turbulent flow in the ground loop.

  2. A geothermal loop filled with 20% propylene glycol solution will have a freeze point of approximately:

    Answer: 15°F (-9°C)

    A 20% propylene glycol solution has a freeze protection point of approximately 15°F (-9°C), providing a safety margin below typical minimum EWT targets.

  3. In a two-stage or variable-speed compressor geothermal heat pump, what design advantage does variable capacity provide for residential systems?

    Answer: Better matches part-load demand, improving seasonal efficiency and comfort

    Variable-capacity compressors modulate output to match the actual building load, reducing short-cycling and improving the system's seasonal COP and humidity control.

  4. Which loop configuration is most appropriate for a residential site with limited land area but access to deep drilling?

    Answer: Vertical closed-loop boreholes

    Vertical closed-loop boreholes require a small surface footprint because heat exchange length is achieved by drilling deep rather than spreading horizontally.

  5. What is the purpose of a 'header' in a closed-loop geothermal bore field?

    Answer: It connects multiple parallel borehole loops to a common supply and return manifold

    The header manifold connects individual borehole U-tubes in parallel, balancing flow distribution across the bore field and reducing total pressure drop.

  6. According to IGSHPA guidelines, what is the maximum allowable pressure drop recommended across a residential geothermal ground loop to minimize pump energy?

    Answer: 4 ft WC per 100 ft of pipe

    IGSHPA recommends limiting friction loss to approximately 4 ft of water column per 100 ft of pipe to keep circulating pump power within an energy-efficient range.

  7. A designer is evaluating a pond loop for a residential system. What minimum pond volume (in acre-feet) per ton of system capacity is generally recommended?

    Answer: 1.5 acre-ft per ton

    Approximately 1.5 acre-feet of pond volume per ton of heating/cooling capacity is the commonly cited minimum to provide adequate thermal mass and recovery.

How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy

Sources & references

Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy

  1. igshpa.org — Renewal, fees, eligibility, score validity · verified Oct 2026
  2. csagroup.org — Test delivery, exam format, passing score, renewal, retake policy, score release, time limit, score validity · verified Oct 2026