Fueling Station Operations Flashcards
7 cards from real CNG practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Fueling Station Operations flashcards as text
If a CNG fire ignites at a fueling station, what is the FIRST recommended action?
Answer: Activate the emergency fuel shutoff and evacuate the area
The first priority in a CNG fire is activating the emergency shutoff to cut fuel supply, followed by immediate evacuation and calling 911 — extinguishing a gas fire without stopping flow creates an explosive cloud.
What is the lower explosive limit (LEL) of natural gas (methane) in air?
Answer: 5%
Methane's LEL is approximately 5% by volume in air; below this concentration, the mixture is too lean to ignite.
Which NFPA code is the primary national standard for CNG vehicular fueling system safety?
Answer: NFPA 52
NFPA 52, Vehicular Natural Gas Fuel Systems Code, is the primary standard covering CNG fueling station design, installation, and operational safety.
At what percentage of the LEL should a fixed combustible gas detector alarm at a CNG station?
Answer: 20% LEL
Industry practice sets alarm thresholds at 20% LEL to provide early warning well before gas concentrations reach an ignitable range.
What type of portable fire extinguisher is most appropriate for use at a CNG fueling station?
Answer: Dry chemical ABC-rated extinguisher
ABC dry chemical extinguishers are appropriate at CNG stations because they handle ordinary combustibles, flammable gases/liquids, and energized electrical equipment.
What is the correct action if a CNG dispenser hose coupling begins leaking during an active fueling operation?
Answer: Stop fueling immediately and depressurize the hose before inspecting
A leaking coupling requires an immediate fueling stop and full hose depressurization before any inspection or repair is attempted.
Under NFPA 52, what is the minimum required distance between a CNG dispenser and a building opening (door, window, or air intake)?
Answer: 10 feet
NFPA 52 requires CNG dispensers to be located at least 10 feet from building openings to prevent gas accumulation inside structures.