  1. What causes high discharge pressure in a compressor?

    Answer: Dirty condensers, non-condensable gases, excessive refrigerant charge, high ambient temperature, or restricted condenser airflow

    High discharge (head) pressure results from anything that impairs heat rejection in the condenser: fouled surfaces, air in the system, overcharge, restricted airflow, high ambient temperatures, or faulty condenser fans.

  2. What causes low suction pressure in a compressor?

    Answer: Low refrigerant charge, restricted liquid line, dirty evaporator, low airflow across evaporator, or a stuck expansion valve

    Low suction pressure indicates insufficient refrigerant reaching the evaporator: possible causes include leak (low charge), restriction in the liquid line, fouled evaporator coils, inadequate air/fluid flow, or expansion valve malfunction.

  3. What is the purpose of a vibration isolation system for compressors?

    Answer: To prevent compressor vibration from transmitting to the building structure, piping, and equipment, reducing noise and preventing fatigue failures

    Vibration isolators (spring mounts, rubber pads, flexible piping connections) prevent mechanical vibration from the compressor from damaging piping connections, building structures, and nearby equipment.

  4. What is a Management of Change (MOC) procedure?

    Answer: A systematic process for evaluating and documenting any modifications to equipment, procedures, or materials before implementation to prevent introducing new hazards

    MOC is a PSM requirement ensuring that any change to the refrigeration system (equipment modifications, procedure changes, material substitutions) is evaluated for safety implications before implementation.

  5. What is a Mechanical Integrity (MI) program?

    Answer: A systematic program of inspections, testing, and maintenance to ensure that process equipment operates safely and reliably

    MI programs include documented inspection schedules, pressure vessel testing, piping inspections, safety device testing, equipment maintenance procedures, and quality assurance for repairs and replacements.

  6. What records must an industrial refrigeration operator maintain?

    Answer: Operating logs, maintenance records, inspection reports, PSM/RMP documentation, training records, and incident reports

    Comprehensive recordkeeping is required for regulatory compliance (PSM/RMP) and good operating practice: daily operating logs, maintenance history, inspection results, training documentation, emergency response drills, and incident investigations.