Energy Efficiency & System Optimization Flashcards
6 cards from real CIRO practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Energy Efficiency & System Optimization flashcards as text
What is the relationship between condensing temperature and system energy consumption?
Answer: Higher condensing temperatures increase compressor work and energy consumption; lowering condensing temperature by 1°F saves approximately 1-2% energy
The compressor must work harder to reach higher discharge pressures (higher condensing temperatures). Each 1°F reduction in condensing temperature saves approximately 1-2% in compressor energy, making condenser maintenance critical for efficiency.
How does floating head pressure control save energy?
Answer: By allowing condensing pressure to decrease when ambient conditions permit, reducing compressor work
Floating head pressure allows the system to take advantage of cooler ambient conditions by lowering condensing pressure (and temperature) below the fixed setpoint, reducing compressor energy consumption significantly.
What is the benefit of variable frequency drives (VFDs) on compressor motors?
Answer: VFDs adjust motor speed to match actual load, avoiding the energy waste of running at full speed during partial load conditions
VFDs allow compressors to operate at reduced speed during partial load, closely matching capacity to actual demand. This can save 20-50% of compressor energy compared to constant-speed operation with slide valve unloading.
What impact does evaporator fouling have on system performance?
Answer: Fouled evaporators reduce heat transfer, lower suction pressure, increase compressor run time, and waste energy
Ice buildup, oil accumulation, or debris on evaporator surfaces acts as insulation, reducing heat transfer. The system compensates by running longer at lower suction pressures, significantly increasing energy consumption.
How does proper insulation of refrigerated piping save energy?
Answer: Insulation prevents heat gain into cold pipes and moisture condensation, maintaining system efficiency and preventing ice buildup on pipes
Uninsulated cold piping absorbs heat from the surrounding environment, adding to the cooling load. Proper vapor-barrier insulation prevents both heat gain and moisture condensation, maintaining system efficiency.
What is the optimal evaporator TD (temperature difference) for energy-efficient operation?
Answer: The smallest practical TD that maintains adequate capacity, typically 8-12°F for cold storage
Lower TD means higher suction pressure, which reduces compressor energy. However, TD must be large enough to maintain adequate capacity and heat transfer. The optimal TD balances efficiency with practical cooling needs.