Ventilation, Exhaust Hoods, and Kitchen Fire Suppression Systems Flashcards
6 cards from real CFESA practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Ventilation, Exhaust Hoods, and Kitchen Fire Suppression Systems flashcards as text
What is the key functional difference between a Type I and a Type II commercial kitchen exhaust hood?
Answer: Type I is designed to capture grease-laden vapors and requires a grease filter and fire suppression system; Type II handles only heat and moisture without grease
Type I hoods are rated to capture grease-laden effluent and must incorporate listed grease filters and a fire suppression system. Type II hoods handle heat, steam, and odors from non-grease-producing equipment (dishwashers, ovens with no direct flame exposure) and do not require grease filters or suppression.
A gas range fails to reignite after the kitchen's Ansul fire suppression system discharged. After confirming the gas valve is open, what is the most likely cause?
Answer: The suppression system automatically shut off the gas via a fusible link or electrical interlock that has not been reset
NFPA 96 requires fire suppression systems to incorporate a gas shut-off — either a fusible-link mechanical valve or an electrical solenoid. After a discharge, these devices must be manually reset or the fusible link replaced before gas flow is restored. This is the most common post-discharge service call.
What is 'makeup air' in the context of a commercial kitchen ventilation system, and why is it required?
Answer: Filtered outdoor air introduced to replace the volume exhausted by the hood, preventing negative pressure that would impair hood capture velocity and equipment combustion air
For every cubic foot per minute exhausted by the hood, an equivalent volume must be supplied as makeup air. Without it, the kitchen develops negative pressure: exterior doors become hard to open, hood capture velocity drops, and atmospheric-combustion appliances can experience backdrafting and flame rollout.
Under NFPA 96, how frequently must a commercial kitchen exhaust hood and duct system be inspected and cleaned at a minimum for a high-volume cooking operation such as a 24-hour restaurant with solid fuel or wok cooking?
Answer: Monthly
NFPA 96 Table 11.4 specifies cleaning frequency based on cooking volume and fuel type. High-volume, solid-fuel, and wok cooking operations require monthly inspection and cleaning due to the accelerated grease accumulation that creates fire hazard.
A technician notices that a deep fryer positioned near the edge of the exhaust hood capture area experiences frequent flame impingement and elevated flue temperatures. What is the FIRST corrective action to investigate?
Answer: Verify that the hood overhang dimension and exhaust CFM meet the equipment manufacturer's and NFPA 96 minimum capture velocity requirements for that appliance
Flame instability and elevated temperatures near the hood edge indicate the hood is undersized or positioned incorrectly — insufficient overhang or inadequate CFM means the capture envelope does not fully contain the appliance's effluent plume. This is a code compliance and fire safety issue, not a fryer fault.
What is the required maximum clearance between a listed grease filter and an open flame on cooking equipment below a Type I hood, per NFPA 96?
Answer: 18 inches (457 mm)
NFPA 96 Section 4.2.1 specifies that grease filters must be installed at least 18 inches (457 mm) above cooking surfaces with open flames. This clearance is required to prevent grease filter ignition from direct flame contact.
How this page was made: written with AI tools and published by Nathan Beja, founder of Practice Test Geeks, who is responsible for its content. Exam facts are checked against the official sources listed below. Not reviewed by a subject-matter expert. Editorial policy
Sources & references
Exam facts on this page (fees, format, dates, passing scores) are checked against these official sources; the date is our last check. Editorial policy
- cfesa.com — Test delivery, eligibility, registration, renewal, score validity, exam information · verified Oct 2026