Data Center Power Infrastructure Flashcards
6 cards from real CDCP practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Data Center Power Infrastructure flashcards as text
What is the purpose of a static transfer switch (STS) in a data center power system?
Answer: To automatically transfer an IT load from one power source to another in less than a quarter cycle (4ms or less) without interruption
An STS uses solid-state electronics to transfer critical loads between two independent power sources in less than 4 milliseconds, fast enough that IT equipment does not experience a power interruption.
What is the purpose of an isolation transformer in a data center power distribution system?
Answer: To electrically isolate equipment from the power distribution system, reduce common-mode noise, and provide a separately derived system for grounding
Isolation transformers provide galvanic isolation between primary and secondary circuits, eliminating common-mode noise, providing a new neutral-ground bond, and improving electrical safety.
What does 'kVA' measure in the context of data center power systems, and how does it differ from kW?
Answer: kVA (kilovolt-amperes) measures apparent power including reactive components; kW measures real (active) power. The ratio kW/kVA is the power factor.
kVA is apparent power (voltage × current), while kW is real power (the work-performing component). Power factor (PF) = kW/kVA; modern IT equipment typically has PF of 0.9–0.99.
In a 2N UPS configuration, how is the IT load typically distributed between the two UPS systems during normal operation?
Answer: Each UPS carries 50% of the total IT load, so each operates at 50% capacity and either can support 100% of the load alone if the other fails
In a 2N configuration, both UPS systems are active and each carries half the load, ensuring that if one fails the other can immediately assume 100% of the load without any switching.
What is the function of a power distribution unit (PDU) in a data center?
Answer: To receive high-voltage power from UPS or transformers and distribute it to individual racks at the appropriate voltage and with circuit protection
A PDU takes incoming power from the UPS or facility transformer and distributes it to multiple branch circuits serving individual racks, providing overcurrent protection and often metering.
What is the typical battery runtime design target for data center UPS systems, and why isn't it designed for longer runtimes?
Answer: 10–15 minutes — long enough for generators to start, transfer to load, and stabilize; longer battery runtimes are expensive, heavy, and unnecessary if generators are on-site
UPS batteries are typically sized for 10–15 minutes at full load — sufficient to start and load generators (90–180 seconds) with a comfortable margin. Extended battery runtimes are costly and unnecessary when generators are available.