CDCP Cheat Sheet 2026
The 30 highest-yield CDCP facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.
40 questions
60 min time limit
68.00% to pass
- Which type of optical transceiver form factor is most commonly used in high-density 100GbE data center switch ports today? → QSFP28
- Which data center tier level, as defined by the Uptime Institute, requires N+1 redundancy and provides 99.741% availability? → Tier II
- What is 'stranded power' in a data center context? → Power allocated to a rack but not actually consumed by installed equipment
- Under NFPA 75, what is the maximum allowable fire compartment size for IT equipment rooms protected by automatic sprinklers? → 52,000 square feet
- What are the most detrimental effects of having an excessive number of perforated tiles in a datacenter? → It reduces the overall underfloor pressure, while also reducing overall cooling impact
- Which cooling strategy delivers cooled air directly to the server inlet within or adjacent to the rack, minimizing distribution losses? → In-row cooling
- Which metric does DCIM use to measure the ratio of IT equipment energy to total facility energy? → DCIE (Data Center Infrastructure Efficiency)
- Which CCTV camera placement strategy provides the BEST coverage of a data center's server room entrance? → Camera positioned above and behind the entry point facing outward
- What is the main mechanical distinction between computer room air handlers (CRAHs) and CRACs? → CRACs have refrigeration compressors as part of their primary system
- A data center implements 'two-person integrity' (TPI) for access to certain critical areas. What does this policy require? → No individual may enter or work in the area alone
- A facility manager notices the PUE has risen from 1.45 to 1.68 over three months. What is the MOST likely cause to investigate first? → Cooling system inefficiency or failure
- In data center redundancy notation, what does '2N' mean? → Full duplication of every component — twice the capacity needed to run the load
- Which fire suppression system is most commonly preferred in data centres due to minimal equipment damage? → Clean agent gaseous suppression (e.g., FM-200)
- Which data source is most critical for accurate DCIM floor-plan visualization? → As-built drawings with precise rack coordinates
- Which standard defines the test procedures and performance requirements for UPS systems used in data centers? → IEC 62040-3
- What does PUE (Power Usage Effectiveness) measure in a data center? → The ratio of total facility power to IT equipment power
- Which RAID level provides striping with double distributed parity, tolerating up to two simultaneous drive failures? → RAID 6
- Which type of UPS topology provides the highest level of power protection by always running the load through the inverter? → Double-conversion (online) UPS
- What is the recommended inlet temperature range for most data center server equipment according to ASHRAE A1 class guidelines? → 64–80°F (18–27°C)
- Which cooling approach is most appropriate for ultra-high-density computing pods exceeding 100 kW per rack, such as AI GPU clusters? → Direct liquid cooling (DLC) or immersion cooling delivering liquid directly to components
- Which of the following businesses rent or lease their data center capabilities to other businesses? → Both a and b
- What does 'return loss' measure in a structured cabling link? → Signal energy reflected back toward the transmitter due to impedance mismatches
- When a data center employee's access badge is reported lost or stolen, what is the FIRST action security staff should take? → Immediately deactivate the lost badge in the access control system
- According to the NFPA 75 standard, what is the primary purpose of creating separate, fire-rated compartments or zones within a data center? → To contain a fire within its area of origin and prevent it from spreading to other zones.
- In data centre physical security, what is a mantrap (or airlock)? → A small room with two interlocking doors where only one can open at a time
- What fire detection technology is most effective at detecting slow, smoldering fires in early stages within a data centre? → Very Early Smoke Detection Apparatus (VESDA)
- What does "heat density" mean in terms of the HVAC system of a data center? → The temperature average in an area, but not the entire site.
- Which network topology is most commonly used within a data center to provide redundancy and high availability? → Fat-tree (spine-leaf) topology
- The capacity of a system or component to carry out its necessary operations under specified conditions for a predetermined amount of time is known as . → Reliability
- What kind of fire detection system is suggested for safeguarding a data center? → Heat detector