HVAC/R Certification Exam — Questions and Answers
Question 1: What is the correct method for disposing of old compressor oil removed during system maintenance?
- Mix it with fresh oil and reuse it
- Discard it in a standard trash receptacle
- Pour it down a floor drain
- Dispose of it as hazardous waste through an approved recycling or disposal facility (Correct answer)
Correct answer: Dispose of it as hazardous waste through an approved recycling or disposal facility
Compressor oil from refrigeration systems is considered hazardous waste and must be disposed of through a licensed recycling or hazardous waste facility.
Question 2: What symptom would a technician observe if the reversing valve on a heat pump is stuck in the heating position?
- No heating or cooling available
- Cooling and heating work but efficiency is low
- Compressor overheats only in heating mode
- No cooling in summer, heating works normally (Correct answer)
Correct answer: No cooling in summer, heating works normally
If the reversing valve is stuck in heating mode, the system will heat in both summer and winter, providing no cooling when switched to cooling mode.
Question 3: The fundamental principle of the refrigeration cycle is based on which thermodynamic concept?
- Heat naturally flows from a colder substance to a warmer substance.
- Heat is created by compressing a gas and destroyed by expanding it.
- Subcooling and superheating must always be equal for proper operation.
- The relationship between a fluid's pressure and its boiling point. (Correct answer)
Correct answer: The relationship between a fluid's pressure and its boiling point.
The refrigeration cycle works by manipulating the refrigerant's pressure. By lowering the pressure in the evaporator, its boiling point drops, allowing it to absorb heat. By increasing the pressure in the condenser, its boiling point rises, allowing it to release heat to the warmer outdoor air. This pressure-temperature relationship is key.
Question 4: What is the recommended method for testing a newly brazed joint for leaks before evacuating and charging a system?
- Visual inspection only
- Pressurize with nitrogen and use electronic leak detector or soap bubbles (Correct answer)
- Apply a vacuum and watch the gauge
- Pressurize with refrigerant to 150 psig
Correct answer: Pressurize with nitrogen and use electronic leak detector or soap bubbles
Nitrogen pressure testing with an electronic detector or soap bubbles is safe and code-compliant; using refrigerant for leak testing wastes refrigerant and is prohibited.
Question 5: A variable-speed ECM blower motor does not respond to speed change commands from the control board. The motor runs at one fixed speed only. What is the most likely fault?
- Loss of PWM or DC control signal from the control board (Correct answer)
- Failed run capacitor on the ECM motor
- Open start relay in the motor
- Low-voltage supply to the motor module
Correct answer: Loss of PWM or DC control signal from the control board
ECM motors rely on a PWM or 0–10V DC control signal from the board to vary speed; loss of this signal causes the motor to default to a fixed speed.
Question 6: During a new system startup, the technician measures superheat at 5°F on a fixed-orifice system. What does this indicate?
- The system is properly charged
- The compressor is running at high efficiency
- The system is overcharged (Correct answer)
- The system is undercharged
Correct answer: The system is overcharged
Very low superheat (below the target of ~10°F on most fixed-orifice systems) indicates an overcharge, which risks liquid refrigerant entering the compressor.
Question 7: Which safety control opens the circuit to the compressor contactor coil when refrigerant pressure exceeds the set point?
- Oil pressure switch
- Low-pressure switch
- High-pressure switch (Correct answer)
- Loss-of-charge switch
Correct answer: High-pressure switch
The high-pressure switch is a normally closed safety device that opens to cut power to the contactor coil when discharge pressure exceeds its cut-out setting.
Question 8: When pressure testing a newly installed system with nitrogen, the test pressure for an R-410A system should not exceed:
- 450 psig (Correct answer)
- 600 psig
- 150 psig
- 300 psig
Correct answer: 450 psig
ASHRAE 15 and most manufacturers limit nitrogen pressure testing of R-410A systems to 450 psig (the low-side design pressure) to avoid damaging system components.
Question 9: Which type of copper tubing is required for ACR (Air Conditioning and Refrigeration) refrigerant line sets?
- CPVC plastic tubing
- Dehydrated, nitrogen-charged ACR copper tubing (Correct answer)
- Standard Type M plumbing copper
- Galvanized steel tubing
Correct answer: Dehydrated, nitrogen-charged ACR copper tubing
ACR-grade copper tubing is cleaned, dehydrated, and sealed with nitrogen to prevent moisture and contamination that would damage refrigerant systems.
Question 10: During a maintenance check, the technician notices the outdoor fan motor is drawing more amps than its nameplate rating. What is the most likely cause?
- Refrigerant overcharge
- Low suction pressure
- Failing motor bearings or a failing capacitor (Correct answer)
- Dirty evaporator coil
Correct answer: Failing motor bearings or a failing capacitor
A motor drawing above nameplate amperage usually indicates worn bearings creating drag or a weak start/run capacitor failing to support the motor.
Question 11: When using an electronic leak detector on an air conditioning system, the probe should be moved:
- Directly over the Schrader valves only
- Slowly along the bottom of fittings and connections (Correct answer)
- Rapidly across the entire unit
- Only along the top of refrigerant lines
Correct answer: Slowly along the bottom of fittings and connections
Refrigerant vapor is heavier than air and settles downward, so moving the probe slowly along the bottom of fittings ensures detection of leaking vapors.
Question 12: What is the primary consequence of installing an oversized air conditioning system?
- Improved dehumidification performance
- Extended equipment service life
- Short cycling and poor humidity control (Correct answer)
- Lower monthly energy bills
Correct answer: Short cycling and poor humidity control
An oversized system reaches the thermostat setpoint too quickly, causing it to short cycle and run for insufficient time to remove humidity from the air.
Question 13: On a cooling system with a TXV, the technician measures 12°F subcooling at the condensing unit outlet and 22°F subcooling at the indoor unit inlet. What does this indicate?
- The condenser fan motor is failing
- There is a restriction in the liquid line (Correct answer)
- The system is undercharged
- The system is properly charged
Correct answer: There is a restriction in the liquid line
A significant subcooling rise through the liquid line indicates a restriction (such as a clogged filter drier or kinked line) that is causing a pressure and temperature drop.
Question 14: What is the correct procedure for discharging a capacitor before handling it?
- Allow the unit to sit unpowered for 10 seconds
- Use a 10,000-ohm, 10-watt resistor across the terminals (Correct answer)
- Use needle-nose pliers to short the terminals
- Short the terminals with a screwdriver blade rapidly
Correct answer: Use a 10,000-ohm, 10-watt resistor across the terminals
A resistor safely dissipates the stored charge without the arc that a direct short causes, which can damage terminals and capacitor internals.
Question 15: Which of the following doesn't fit the definition of a compressor?
- Rotary
- Reciprocating
- Screw
- Lateral (Correct answer)
Correct answer: Lateral
The question asks which term does not fit the definition of a compressor type. Rotary, screw, and reciprocating are all recognized and common types of compressors used in various applications, including air conditioning systems. 'Lateral' is not a classification or type of compressor mechanism.
Question 16: The engine may run excessively cold, according to Technician A, if the thermostat is broken. The thermostat can generate a pinging or pounding noise if it is jammed closed, according to technician B. Who is correct?
- Neither Technician A nor B
- Technician A only
- Technician B only
- Both Technician A and B (Correct answer)
Correct answer: Both Technician A and B
Technician A is correct because a thermostat stuck open will allow coolant to continuously flow through the radiator, preventing the engine from reaching its optimal operating temperature and causing it to run excessively cold. Technician B is also correct; a thermostat jammed closed will restrict coolant flow, leading to severe engine overheating and potential pinging or pounding noises from boiling coolant and pressure buildup. Both technicians accurately describe potential thermostat malfunctions and their symptoms.
Question 17: A technician needs to recover R-410A from a residential split system. To prevent cross-contamination and ensure safety, what is the most critical first step before connecting the recovery machine?
- Ensure the recovery machine is properly grounded.
- Purge the recovery machine and hoses with nitrogen.
- Verify the recovery cylinder has enough capacity for the entire system charge.
- Check the refrigerant type in the system and on the recovery cylinder. (Correct answer)
Correct answer: Check the refrigerant type in the system and on the recovery cylinder.
Mixing different types of refrigerants in a recovery cylinder is dangerous and illegal. It can create a high-pressure, unpredictable mixture and makes the refrigerant impossible to reclaim. Therefore, always verify the system refrigerant matches the designated recovery cylinder before starting the recovery process.
Question 18: A technician is installing a split system where the line set run is 75 feet — 25 feet longer than the manufacturer's standard. What adjustment is typically required?
- Increase blower speed by one tap
- Add refrigerant charge per the manufacturer's extended line set table (Correct answer)
- Increase the thermostat setpoint by 2°F
- Install a second TXV in series
Correct answer: Add refrigerant charge per the manufacturer's extended line set table
Manufacturers publish refrigerant add-per-foot tables for line sets longer than the tested standard length to compensate for the additional volume.
Question 19: What are some common problems that can be fixed by an HVAC repair?
- Problem with air conditioner
- Electrical problems (Correct answer)
- Heating problems
- Cooling problems
Correct answer: Electrical problems
HVAC repair services address a broad spectrum of issues, and electrical problems are among the most frequent culprits for system malfunctions. These can range from faulty wiring, tripped circuit breakers, and capacitor failures to issues with thermostats and control boards. Addressing these electrical components is critical for the safe and proper operation of both heating and cooling systems.
Question 20: A condensate drain line is routed through an unconditioned attic. What additional measure is required by most building codes?
- Use schedule 80 PVC instead of schedule 40
- Increase the drain line diameter to 1 inch
- Insulate the drain line to prevent sweating and dripping (Correct answer)
- Install a condensate pump at the air handler
Correct answer: Insulate the drain line to prevent sweating and dripping
Uninsulated condensate drain lines in hot unconditioned spaces can sweat and drip, causing water damage and mold — insulation prevents this.
Question 21: What is the minimum recommended vacuum level (microns) before closing service valves and charging a residential AC system?
- 2000 microns
- 500 microns (Correct answer)
- 5000 microns
- 1000 microns
Correct answer: 500 microns
Most manufacturers and industry standards require a vacuum of 500 microns or lower to ensure all moisture and non-condensables are removed.
Question 22: A technician is recovering refrigerant from a system with a confirmed compressor burnout. Which of the following actions is MOST critical to protect the recovery equipment?
- Using an in-line filter-drier on the recovery hose. (Correct answer)
- Recovering only in the vapor phase to avoid liquid slugging.
- Chilling the recovery cylinder in an ice bath.
- Operating the recovery machine in a well-ventilated area.
Correct answer: Using an in-line filter-drier on the recovery hose.
A compressor burnout creates acids and sludge in the refrigerant and oil. Using an in-line filter-drier during recovery is essential to capture these contaminants, protecting the recovery machine's compressor, seals, and sensors from damage.
Question 23: What does a high delta-T (temperature difference) across the evaporator coil typically indicate?
- Overcharged refrigerant
- Good system performance with proper heat absorption (Correct answer)
- Dirty condenser coil
- Low refrigerant charge
Correct answer: Good system performance with proper heat absorption
A temperature difference of 16–22°F across the evaporator coil typically indicates the system is properly absorbing heat and operating efficiently.
Question 24: What safety precaution must be taken when handling R-134a refrigerant in liquid form?
- Wear flame-resistant gloves
- Ground yourself to prevent static discharge
- Use a respirator rated for organic vapors
- Wear safety goggles and insulated gloves to prevent frostbite (Correct answer)
Correct answer: Wear safety goggles and insulated gloves to prevent frostbite
Liquid R-134a evaporates rapidly on contact with skin or eyes, causing severe frostbite and injury; PPE including goggles and thermal-insulating gloves is required.
Question 25: A technician is troubleshooting an air handler that blows warm air in cooling mode. The compressor and condenser fan are running. What electrical component failure could cause this symptom?
- Open circuit in the reversing valve solenoid (heat pump) (Correct answer)
- Shorted contactor holding coil
- Open circuit in the indoor blower capacitor
- Failed thermostat R-terminal fuse
Correct answer: Open circuit in the reversing valve solenoid (heat pump)
On a heat pump, an open reversing valve solenoid coil prevents the valve from switching to cooling mode, causing the system to deliver warm air.
Question 26: A compressor is wired to a 208/230V disconnect. Which wire gauge is required for a 30-amp circuit per NEC?
- 14 AWG
- 12 AWG
- 8 AWG
- 10 AWG (Correct answer)
Correct answer: 10 AWG
NEC requires 10 AWG copper conductors for a 30-amp circuit at standard ambient temperatures.
Question 27: A technician is checking subcooling on a fixed-orifice system. Where should subcooling be measured?
- At the suction line near the compressor
- At the inlet of the evaporator
- At the liquid line service valve near the condenser outlet (Correct answer)
- At the discharge line near the compressor
Correct answer: At the liquid line service valve near the condenser outlet
Subcooling is measured at the liquid line leaving the condenser, comparing the actual temperature to the saturation temperature at that pressure.
Question 28: What micron level must be achieved and held during system evacuation before charging with refrigerant?
- 2,000 microns
- 10,000 microns
- 500 microns or lower (Correct answer)
- 5,000 microns
Correct answer: 500 microns or lower
Industry standards require pulling the system down to 500 microns or lower and verifying the level holds to confirm adequate moisture removal and leak integrity.
Question 29: A technician finds the AC compressor cycling on and off rapidly (short cycling). What is the most likely cause?
- Clogged expansion valve
- Faulty blower motor resistor
- Overcharged system
- Low refrigerant triggering the low-pressure cutoff switch (Correct answer)
Correct answer: Low refrigerant triggering the low-pressure cutoff switch
Low refrigerant causes system pressure to drop below the low-pressure switch threshold, cutting the compressor off; it restarts once pressure rises slightly, causing rapid cycling.
Question 30: How often should air conditioning system air filters typically be inspected or replaced in a residential application?
- Only when the system stops cooling
- Once every 2 years
- Every 1–3 months depending on usage and filter type (Correct answer)
- At the time of installation only
Correct answer: Every 1–3 months depending on usage and filter type
Residential AC air filters should be inspected monthly and replaced every 1–3 months to maintain airflow and system efficiency.
Question 31: What type of tool is used to open the fan cage?
- Hex key and a wrench
- Hammer
- Knife
- Screwdriver and a wrench (Correct answer)
Correct answer: Screwdriver and a wrench
To safely open the fan cage of an outdoor air conditioning condenser unit, you typically need basic hand tools such as a screwdriver and a wrench. A screwdriver is used to remove the retaining screws that secure the cage, while a wrench might be necessary for any nuts or bolts. These tools allow for proper disassembly to access the fan motor or clean internal components.
Question 32: Which tool is used to verify that a crankcase heater on a compressor is functioning properly?
- Manifold gauge set
- Clamp-style ammeter or infrared thermometer (Correct answer)
- Vacuum pump
- Refrigerant scale
Correct answer: Clamp-style ammeter or infrared thermometer
A clamp-style ammeter measures the small current draw of the crankcase heater, while an infrared thermometer confirms the heater is producing heat at the compressor base.
Question 33: Which component's failure would most likely cause high superheat AND high subcooling simultaneously?
- Overcharged refrigerant
- Restricted liquid line or filter drier (Correct answer)
- Failed condenser fan motor
- Open suction service valve
Correct answer: Restricted liquid line or filter drier
A restriction in the liquid line or a clogged filter drier causes refrigerant to back up (high subcooling) before the restriction and starve the evaporator (high superheat) after it.
Question 34: A technician replaces a contactor on a condensing unit. After the repair, the compressor hums but does not start. What is the most likely cause?
- Open high-pressure switch
- Failed run capacitor (Correct answer)
- Clogged filter drier
- Defective thermostat
Correct answer: Failed run capacitor
A humming compressor that won't start typically indicates a failed run or start capacitor that is not providing the necessary starting torque.
Question 35: What is the recommended method for sizing a replacement air conditioner when no prior load data is available?
- Match the existing system's capacity exactly
- Apply the rule of 500 square feet per ton
- Perform a proper Manual J load calculation (Correct answer)
- Install one size larger for added comfort margin
Correct answer: Perform a proper Manual J load calculation
A proper Manual J load calculation is always the correct approach because existing equipment may have been incorrectly sized, and building conditions may have changed.
Question 36: What is ACCA Manual J used for in the HVAC industry?
- Sizing commercial duct systems
- Performing residential load calculations (Correct answer)
- Selecting refrigerant recovery equipment
- Calculating EPA refrigerant allowances
Correct answer: Performing residential load calculations
ACCA Manual J is the industry-standard method for calculating residential heating and cooling loads to properly size HVAC equipment.
Question 37: What is the purpose of checking and tightening electrical connections during preventive maintenance?
- To reduce refrigerant charge requirements
- To increase system airflow
- To lower the superheat setting
- To prevent resistance heating, arcing, and component failure (Correct answer)
Correct answer: To prevent resistance heating, arcing, and component failure
Loose electrical connections create resistance, generate heat, cause arcing, and can lead to component or control board failures.
Question 38: When setting up a manifold gauge set on an R-410A system, the technician should use hoses rated for at least:
- 1,000 psi working pressure
- 300 psi working pressure
- 500 psi working pressure
- 800 psi working pressure (Correct answer)
Correct answer: 800 psi working pressure
R-410A operates at pressures roughly 60–70% higher than R-22; hoses rated at 800 psi working pressure (4,000 psi burst) are the minimum standard.
Question 39: A technician is preparing to evacuate a system after a major repair. Before starting the vacuum pump, it is critical to:
- Change the oil in the vacuum pump.
- Ensure the system pressure is at 0 psig or below. (Correct answer)
- Install a new filter-drier.
- Warm the refrigerant in the system to vaporize any liquid.
Correct answer: Ensure the system pressure is at 0 psig or below.
A vacuum pump is designed to remove air and non-condensables from a system at very low pressures; it is not a recovery machine. Connecting a vacuum pump to a pressurized system can damage the pump and cause an illegal release of refrigerant into the atmosphere.
Question 40: A technician installs a new 2-ton split system and finds the existing ductwork was designed for a 1.5-ton system. What is the most likely result?
- Reduced refrigerant charge requirement
- Improved comfort due to higher airflow
- Higher static pressure, reduced airflow, poor efficiency and comfort (Correct answer)
- Faster system response time
Correct answer: Higher static pressure, reduced airflow, poor efficiency and comfort
Undersized ductwork increases external static pressure, restricts airflow, reduces system efficiency, and can cause the evaporator coil to freeze.
Question 41: When installing a split-system AC, the indoor air handler should be level or slightly tilted in which direction?
- Perfectly level in all directions
- Tilted toward the refrigerant line set
- Tilted slightly away from the drain outlet
- Tilted slightly toward the drain outlet (Correct answer)
Correct answer: Tilted slightly toward the drain outlet
The air handler should pitch slightly toward the condensate drain outlet so gravity assists condensate removal and prevents pan overflow.
Question 42: Which of the following factors does NOT significantly affect a building's cooling load?
- Window area and orientation
- Number of occupants
- Interior wall paint color (Correct answer)
- Attic insulation levels
Correct answer: Interior wall paint color
Interior paint color has a negligible effect on cooling load; exterior surface colors can affect solar absorptance, but interior colors do not meaningfully impact heat gain.
Question 43: A car AC condenser fan runs only when the AC is on. The engine is overheating in traffic. What is the likely fault?
- Blown AC fuse
- Engine coolant temperature sensor failed
- Low refrigerant pressure
- Condenser fan relay or control wiring not triggering the fan for engine cooling (Correct answer)
Correct answer: Condenser fan relay or control wiring not triggering the fan for engine cooling
The condenser fan should activate both for AC operation and independently when coolant temperature reaches a threshold; a relay or wiring fault can disable the cooling-mode trigger.
Question 44: What is the recommended method to verify proper refrigerant charge on a fixed-orifice (piston) metering device system?
- Target a superheat of 10–18°F at the evaporator outlet under standard conditions (Correct answer)
- Weigh in the factory charge and do not check further
- Use only a sight glass to confirm clear flow
- Check subcooling at the condenser outlet only
Correct answer: Target a superheat of 10–18°F at the evaporator outlet under standard conditions
Fixed-orifice systems are charged using superheat method, typically targeting 10–18°F at the evaporator outlet to ensure proper refrigerant feed without flooding.
Question 45: What is the purpose of the C (common) terminal on a 24V thermostat circuit?
- It provides the return path for 24V AC from the transformer secondary (Correct answer)
- It signals the reversing valve
- It connects to the outdoor unit high-pressure switch
- It carries the high-voltage power to the compressor
Correct answer: It provides the return path for 24V AC from the transformer secondary
The C wire completes the 24V control circuit by returning current to the transformer's secondary common, allowing smart thermostats and other loads to operate continuously.
Question 46: A technician finds a blown 3-amp control fuse repeatedly. What is the correct diagnostic approach?
- Replace the thermostat immediately
- Replace the transformer and fuse together
- Replace with a 5-amp fuse for a permanent fix
- Disconnect control wiring sections to isolate the short before replacing the fuse (Correct answer)
Correct answer: Disconnect control wiring sections to isolate the short before replacing the fuse
Isolating sections of the control circuit identifies the shorted wire or component causing the overcurrent before replacing the fuse.
Question 47: When brazing copper refrigerant lines, nitrogen should be flowing through the lines at what approximate pressure?
- 2–5 psig (Correct answer)
- 15–20 psig
- 50 psig
- 0 psig (off)
Correct answer: 2–5 psig
A low nitrogen purge of 2–5 psig displaces oxygen inside the tubing to prevent copper oxide scale formation without blowing out the brazing alloy.
Question 48: A technician measures suction pressure that is too high and discharge pressure that is too low. What is the most likely cause?
- Faulty compressor valves (Correct answer)
- Overcharged system
- Low refrigerant charge
- Restricted liquid line
Correct answer: Faulty compressor valves
Faulty compressor valves (worn or leaking) allow high-pressure gas to bypass back to the suction side, raising suction pressure and lowering discharge pressure.
Question 49: A refrigerant sight glass shows bubbles even though the system appears to have adequate charge. What could cause this besides low charge?
- Condenser fan running too fast
- High ambient temperature
- Overcharged system
- Pressure drop across a restriction in the liquid line (Correct answer)
Correct answer: Pressure drop across a restriction in the liquid line
A restriction in the liquid line causes a pressure drop that can flash refrigerant into vapor, producing bubbles in the sight glass even with sufficient charge.
Question 50: A technician measures a compressor's amp draw and finds it is above the rated full-load amps (FLA). Which condition would most likely cause this?
- Low suction pressure from refrigerant undercharge
- High condensing temperature due to poor heat rejection (Correct answer)
- Open run capacitor
- Low line voltage
Correct answer: High condensing temperature due to poor heat rejection
High condensing temperatures increase the pressure ratio the compressor must work against, forcing it to draw more current than its rated FLA.
Question 51: What does a high-side pressure reading significantly above normal indicate during AC diagnosis?
- Low refrigerant charge
- Faulty expansion valve stuck open
- Restricted or failing condenser (Correct answer)
- Compressor clutch slipping
Correct answer: Restricted or failing condenser
Abnormally high discharge-side pressure typically points to poor condenser airflow, a dirty condenser coil, or a failing condenser fan that prevents heat rejection.
Question 52: To minimize the release of refrigerant when connecting and disconnecting gauges, EPA regulations require service hoses to be equipped with which of the following?
- Color-coded grips for easy identification.
- A minimum length of six feet for safety.
- Low-loss fittings or shut-off valves. (Correct answer)
- Brass fittings to prevent corrosion.
Correct answer: Low-loss fittings or shut-off valves.
EPA regulations under Section 608 mandate that hoses used for servicing, recovering, and charging must be equipped with low-loss fittings or valves that close automatically when the hose is disconnected. This is to trap the refrigerant within the hose and prevent it from being released into the atmosphere.
Question 53: During a new split-system installation, which of the following practices is critical for ensuring proper oil return to the compressor and preventing liquid slugging, especially with long line sets?
- Using a pipe bender to create sharp 90-degree turns
- Installing the suction line with a continuous downward slope from the evaporator to the condenser
- Ensuring the suction line is fully insulated and properly supported (Correct answer)
- Ensuring the liquid line is insulated along its entire length
Correct answer: Ensuring the suction line is fully insulated and properly supported
The suction line carries cool refrigerant gas and entrained oil back to the compressor. It must be fully insulated to prevent the gas from absorbing excess heat, which would reduce system efficiency and capacity. Proper insulation also prevents condensation from forming on the outside of the pipe. Proper support prevents sags where oil could become trapped.
Question 54: When performing a maintenance inspection, a technician finds that the evaporator drain pan is filled with algae. What is the recommended corrective action?
- Replace the entire air handler unit
- Clean the pan and treat it with condensate pan tablets or diluted bleach, then ensure the drain line flows freely (Correct answer)
- Add more refrigerant to lower the coil temperature and kill the algae
- Ignore it as long as the drain line is not blocked
Correct answer: Clean the pan and treat it with condensate pan tablets or diluted bleach, then ensure the drain line flows freely
Algae and slime in the condensate pan should be cleaned out and treated with biocide tablets or diluted bleach to prevent drain line clogs and microbial growth.
Question 55: When charging a system by weight, the technician should zero the refrigerant scale:
- Only if the manufacturer requires it
- Before connecting the hose, with the empty hose weight accounted for (Correct answer)
- After connecting the charging hose to the cylinder
- After opening the cylinder valve
Correct answer: Before connecting the hose, with the empty hose weight accounted for
Zeroing the scale with the hose already attached accounts for the hose weight, so the display shows only the refrigerant transferred rather than hose plus refrigerant.
Question 56: Which safety device opens on a rise in discharge pressure and automatically resets when pressure drops?
- Thermistor
- Low-pressure switch
- High-pressure switch (auto-reset) (Correct answer)
- Fusible plug
Correct answer: High-pressure switch (auto-reset)
An auto-reset high-pressure switch opens the control circuit when discharge pressure exceeds its setpoint and closes again once pressure falls below the reset point.
Question 57: When installing a condensing unit on a rooftop, which mounting concern is most important for long-term reliability?
- The unit must be at least 10 feet from the roof edge
- The unit must face north to avoid sun exposure
- The unit must be level to ensure proper compressor oil lubrication (Correct answer)
- The disconnect must be within 5 feet of the unit
Correct answer: The unit must be level to ensure proper compressor oil lubrication
A level condensing unit ensures the compressor crankcase maintains proper oil level for lubrication; an unlevel unit can cause oil to pool away from the oil pickup.
Question 58: When running refrigerant line sets through walls or floors, technicians must use:
- Metal strapping without cushioning
- Standard drywall anchors only
- PVC conduit rated for gas service
- Grommets or bushings to protect tubing from abrasion (Correct answer)
Correct answer: Grommets or bushings to protect tubing from abrasion
Grommets or bushings protect copper refrigerant tubing from abrasion at wall penetrations, preventing wear-through that could cause leaks.
Question 59: Which condition is indicated by oil streaks or staining around refrigerant line fittings and joints?
- High oil concentration in the refrigerant
- Normal oil migration through the system
- Condensation from humidity
- Refrigerant and oil leak at that location (Correct answer)
Correct answer: Refrigerant and oil leak at that location
Oil streaks at joints indicate refrigerant is leaking there, since refrigerant oil escapes along with refrigerant gas through any leak point.
Question 60: A condensing unit is located in a pit below grade level. What is the primary concern with this installation?
- Refrigerant lines will be too short
- The unit cannot be properly leveled
- Hot air discharge will recirculate into the unit, reducing efficiency and capacity (Correct answer)
- The electrical disconnect is inaccessible
Correct answer: Hot air discharge will recirculate into the unit, reducing efficiency and capacity
A condensing unit in a below-grade pit tends to trap its own hot discharge air, causing high head pressure, reduced efficiency, and potential high-pressure lockout.
Question 61: Which component in a gas furnace/AC system directly controls when the indoor blower comes on after heating ignition?
- Thermostat R terminal
- Fan limit switch or control board fan delay (Correct answer)
- Pressure switch
- Contactor coil
Correct answer: Fan limit switch or control board fan delay
A fan limit switch or control board fan-delay timer delays blower startup until the heat exchanger warms up, preventing cold air distribution.
Question 62: To accurately evaluate total system airflow and diagnose potential restrictions in ductwork, which of the following measurements is most essential?
- Amperage draw of the indoor blower motor
- Total external static pressure (Correct answer)
- Temperature drop across the evaporator coil
- Velocity pressure in the return duct
Correct answer: Total external static pressure
Total external static pressure is the measurement of resistance (pressure) the blower must work against in both the supply and return ducts. A reading higher than the manufacturer's specification indicates a restriction to airflow, such as a dirty filter, clogged coil, or undersized ducts.
Question 63: In load calculations, the U-value of a building assembly describes which property?
- The overall heat transfer coefficient of the assembly (Correct answer)
- The thermal resistance of the insulation layer
- The air leakage rate through the assembly
- The solar absorptance of the exterior surface
Correct answer: The overall heat transfer coefficient of the assembly
U-value is the overall heat transfer coefficient, expressing how much heat flows through an assembly per square foot per degree of temperature difference; it is the mathematical inverse of R-value.
Question 64: In a compressor circuit that utilizes a potential relay, what is the relay's primary function?
- To delay the restart of the compressor after a power interruption.
- To disconnect the start capacitor from the circuit once the motor approaches full speed. (Correct answer)
- To protect the compressor from low voltage conditions.
- To energize the condenser fan motor simultaneously with the compressor.
Correct answer: To disconnect the start capacitor from the circuit once the motor approaches full speed.
A potential relay is used with a start capacitor to provide high starting torque for a motor. The relay's coil senses the back-EMF (voltage) generated across the motor's start winding as it speeds up. When this voltage reaches a predetermined level (typically around 75% of full speed), the relay's normally closed contacts open, taking the start capacitor out of the circuit to prevent it from overheating and failing.
Question 65: A customer with a heat pump complains that it is blowing warm air when the thermostat is set to 'cool'. A technician on-site confirms the outdoor unit is running, but the larger, insulated refrigerant line (the suction line) is hot. Which of the following is the most probable cause?
- A reversing valve stuck in heat mode (Correct answer)
- An undercharged system
- A clogged filter-drier
- A failed condenser fan motor
Correct answer: A reversing valve stuck in heat mode
When a heat pump is stuck in heating mode, the reversing valve fails to switch the flow of refrigerant. [2] The system operates as if it's heating, making the outdoor coil the evaporator and the indoor coil the condenser. This causes the suction line, which is connected to the outdoor coil, to become a hot gas line, resulting in warm air being delivered indoors despite the call for cooling. [15, 16]
Question 66: Which NEC article specifically covers the installation of air conditioning and refrigerating equipment?
- Article 210
- Article 250
- Article 440 (Correct answer)
- Article 430
Correct answer: Article 440
NEC Article 440 specifically addresses air conditioning and refrigerating equipment, including hermetic refrigerant motor-compressors.
Question 67: A technician finds a burned 5-amp fuse on the control board. After replacing it, the fuse blows immediately. What is the correct next step?
- Install a higher-rated fuse
- Check all 24V control wiring for a short to ground (Correct answer)
- Replace the control board
- Measure high-voltage supply to the board
Correct answer: Check all 24V control wiring for a short to ground
An immediately blown fuse indicates a short in the low-voltage circuit; the wiring must be traced to find the short before replacing the fuse again.
Question 68: What is the correct procedure when adding refrigerant to a system equipped with a TXV metering device?
- Charge by subcooling only at the condenser
- Add refrigerant until sight glass clears
- Charge by weight or target superheat at the evaporator outlet (Correct answer)
- Charge to manufacturer's listed operating pressure only
Correct answer: Charge by weight or target superheat at the evaporator outlet
TXV systems are best charged by weight per manufacturer specs or by targeting correct superheat, as sight glass clearing is not a reliable method for TXV systems.
Question 69: Which of the following defines the process of 'Reclamation' according to the EPA?
- Removing refrigerant from a system into an external container.
- Cleaning refrigerant for reuse by separating oil and filtering it.
- Processing used refrigerant to meet the purity standards for new refrigerant gas. (Correct answer)
- Transferring recovered refrigerant to a different system owned by the same person.
Correct answer: Processing used refrigerant to meet the purity standards for new refrigerant gas.
The EPA defines reclamation as the processing of used refrigerant to at least the purity level specified in AHRI Standard 700. This process must be done by an EPA-certified reclaimer and verifies the refrigerant meets the standards for new (virgin) product.
Question 70: A compressor has a burnt motor winding. After replacing it, what additional step is critical before restarting?
- Increasing refrigerant charge by 10%
- Bypassing the crankcase heater
- Adding extra oil to the compressor
- Flushing the system to remove acid and debris (Correct answer)
Correct answer: Flushing the system to remove acid and debris
A burnt motor leaves acid contamination that must be flushed out and a liquid-line suction filter-drier installed to prevent damage to the new compressor.
Question 71: What is the role of the AC pressure cycling switch found in some orifice tube systems?
- It cycles the compressor on and off to prevent evaporator freeze-up (Correct answer)
- It controls the condenser fan speed
- It limits blower motor speed at high pressure
- It opens the high-side relief valve under overpressure
Correct answer: It cycles the compressor on and off to prevent evaporator freeze-up
The pressure cycling switch monitors low-side pressure and cuts the compressor when pressure drops to the freeze point, then restarts it once pressure rises, regulating evaporator temperature.
Question 72: When brazing copper refrigerant lines, nitrogen should be flowing through the tubing during the brazing process to:
- Increase braze filler flow rate
- Purge refrigerant oil from the line
- Prevent oxidation (scaling) inside the copper tubing (Correct answer)
- Speed up the cooling process after brazing
Correct answer: Prevent oxidation (scaling) inside the copper tubing
Flowing dry nitrogen through copper tubing during brazing displaces oxygen, preventing copper oxide scale formation that could contaminate the refrigerant system.
Question 73: A homeowner reports the new system cools well but the house feels humid. Airflow measurements confirm CFM is above manufacturer specifications. What is the recommended corrective action?
- Increase the thermostat setpoint by 2°F
- Add refrigerant charge to improve latent capacity
- Install a larger condenser
- Reduce blower speed to allow the coil more contact time for dehumidification (Correct answer)
Correct answer: Reduce blower speed to allow the coil more contact time for dehumidification
Excessive airflow reduces coil contact time, limiting latent (moisture removal) capacity; reducing blower speed lowers coil temperature and increases dehumidification.
Question 74: What does a nitrogen purge during brazing accomplish?
- Removes moisture from the atmosphere
- Pressurizes the system to check for leaks
- Increases the melting temperature of the solder
- Prevents oxidation and carbon scale from forming inside the copper tubing (Correct answer)
Correct answer: Prevents oxidation and carbon scale from forming inside the copper tubing
Flowing dry nitrogen through the tubing during brazing displaces oxygen, preventing the formation of copper oxides (scale) that can contaminate the system.
Question 75: In a residential load calculation, what category includes heat generated by occupants, lighting, and household appliances?
- Internal heat gain (Correct answer)
- Infiltration heat gain
- Conductive heat gain
- Solar heat gain
Correct answer: Internal heat gain
Internal heat gain accounts for heat produced by sources inside the conditioned space, including people, lighting fixtures, and appliances such as ovens and electronics.
Question 76: A technician is troubleshooting a compressor that hums for a few seconds and then trips the thermal overload. After safely disconnecting power and discharging the capacitor, a multimeter check shows the capacitor's microfarad (µF) reading is well below its rating. What is the most appropriate next step?
- Ohm out the compressor windings.
- Add refrigerant to the system.
- Replace the run capacitor. (Correct answer)
- Replace the contactor.
Correct answer: Replace the run capacitor.
The symptoms of humming followed by tripping on overload are classic signs of a failed run capacitor. [20, 24, 29] The capacitor provides the necessary phase-shifted voltage to create starting torque for the compressor motor. Since the capacitor test confirmed it is faulty, the next logical step is to replace it.
Question 77: What is 'triple evacuation' (also called 'three-step evacuation') used for?
- Evacuating three separate refrigerant circuits simultaneously
- Removing moisture more effectively by breaking vacuum with dry nitrogen between pulls (Correct answer)
- Testing system performance at three different load conditions
- Charging the system in three stages to prevent slugging
Correct answer: Removing moisture more effectively by breaking vacuum with dry nitrogen between pulls
Triple evacuation involves pulling vacuum, breaking with dry nitrogen, then repeating twice more — each cycle draws out more moisture than a single long pull.
Question 78: Which component in a car AC system is responsible for removing moisture from the refrigerant?
- Expansion valve
- Condenser
- Evaporator
- Receiver-drier (Correct answer)
Correct answer: Receiver-drier
The receiver-drier contains desiccant material that absorbs moisture from the refrigerant, preventing ice formation and acid contamination.
Question 79: What does the 'diversity factor' account for in commercial HVAC load calculations?
- The variety of refrigerants approved for use in the system
- The number of different mechanical zones within the building
- The range of outdoor temperatures the system must handle throughout the year
- The recognition that not all loads peak simultaneously, allowing reduced total system capacity (Correct answer)
Correct answer: The recognition that not all loads peak simultaneously, allowing reduced total system capacity
The diversity factor reduces the calculated peak load because in large buildings, all occupants, lighting, and equipment rarely reach their maximum values at the exact same time, allowing for more economical system sizing.
Question 80: What is subcooling in an air conditioning system and why is it measured?
- The temperature drop across the evaporator coil
- The cooling of the compressor motor by suction gas
- The difference between supply and return air temperatures
- The degrees the liquid refrigerant is cooled below its condensing temperature, used to verify proper charge and condenser performance (Correct answer)
Correct answer: The degrees the liquid refrigerant is cooled below its condensing temperature, used to verify proper charge and condenser performance
Subcooling measures how many degrees below its saturation point the liquid refrigerant has been cooled, and is used to confirm correct refrigerant charge and condenser effectiveness.
Question 81: Which of the following is the most common cause of reduced airflow across the evaporator coil in a residential air conditioning system?
- An oversized return duct.
- A dirty or clogged air filter. (Correct answer)
- A malfunctioning thermostat.
- A refrigerant undercharge.
Correct answer: A dirty or clogged air filter.
A dirty air filter creates a significant obstruction in the return air path, increasing the static pressure the blower must work against. This is the most frequent cause of reduced airflow in residential systems. This condition can lead to an iced-over evaporator coil, reduced cooling capacity, and increased energy consumption.
Question 82: What is the primary purpose of an ACCA Manual D calculation?
- Selecting thermostat setpoints for efficiency
- Calculating the correct refrigerant charge
- Determining residential heating and cooling loads
- Designing and sizing the duct distribution system (Correct answer)
Correct answer: Designing and sizing the duct distribution system
ACCA Manual D is the industry standard for residential duct system design, providing methods to size ducts so that the correct amount of conditioned air reaches each room.
Question 83: A technician measures the outdoor ambient temperature at 95°F. What is the expected normal operating range for high-side (discharge) pressure on an R-410A system?
- 450–500 PSIG
- 200–230 PSIG
- 150–175 PSIG
- 380–420 PSIG (Correct answer)
Correct answer: 380–420 PSIG
For R-410A at 95°F ambient, normal high-side (condensing) pressure is typically in the 380–420 PSIG range.
Question 84: A customer complains of a loud "banging" or "popping" noise from their rectangular metal ductwork shortly after the blower motor starts and stops. What is the most probable cause of this noise?
- Debris such as a loose screw rattling inside the duct.
- Excessive air velocity causing the registers to vibrate.
- The use of flexible duct connectors at the plenums.
- Undersized or inadequately supported ductwork experiencing "oil canning." (Correct answer)
Correct answer: Undersized or inadequately supported ductwork experiencing "oil canning."
This phenomenon, known as "oil canning," occurs when large, flat sections of metal ductwork flex due to changes in air pressure. When the blower starts, the duct pressurizes and bows outward; when it stops, it relaxes inward, creating a loud bang or pop. This is often caused by undersized ducts creating high static pressure or duct walls that are too thin or lack proper cross-bracing for support.
Question 85: What could you do to a component of air conditioning equipment if you're not familiar with it?
- Use a voltage tester
- Change the filter
- Call a professional (Correct answer)
- Check the insulation
Correct answer: Call a professional
If you are unfamiliar with a specific component of air conditioning equipment, the safest and most recommended course of action is to contact a professional HVAC technician. Attempting to repair or tamper with unfamiliar parts can lead to further damage, personal injury, or voiding warranties. Professionals possess the necessary expertise, specialized tools, and safety training to diagnose and fix issues correctly.
Question 86: What is the recommended minimum coil cleaning frequency for a residential split-system AC under normal operating conditions?
- Once per year (Correct answer)
- Only when ice forms on the coil
- Every 5 years
- Every 10 years
Correct answer: Once per year
Evaporator and condenser coils should be cleaned at least once per year to prevent dirt buildup that reduces heat transfer.
Question 87: What type of heat gain is caused by heat transferring through walls, roofs, and floors due to a temperature difference?
- Solar heat gain
- Internal heat gain
- Conductive heat gain (Correct answer)
- Latent heat gain
Correct answer: Conductive heat gain
Conductive heat gain occurs when heat flows through solid building materials from a warm exterior surface to a cooler interior, governed by the material's U-value and the temperature difference.
Question 88: After evacuating a system to 500 microns, a technician isolates the vacuum pump and performs a decay test. The micron gauge reading slowly rises before stabilizing at 1,500 microns. What does this most likely indicate?
- The vacuum pump is faulty and requires service.
- There is still moisture boiling off within the system. (Correct answer)
- The system has a large leak to the atmosphere.
- The micron gauge is not calibrated correctly.
Correct answer: There is still moisture boiling off within the system.
A slow rise in vacuum that eventually levels off is a classic sign of moisture remaining in the system. The moisture boils under the deep vacuum, turning into vapor and raising the pressure until all the liquid has boiled off. A large leak would cause the pressure to continue rising steadily toward atmospheric pressure.
Question 89: A technician is testing a potential relay used in a hard start kit. At what point should the potential relay open the start capacitor circuit?
- When the motor reaches approximately 75% of its synchronous speed (Correct answer)
- When discharge pressure exceeds the high-pressure switch set point
- When line voltage is applied to the compressor
- When the run capacitor reaches full charge
Correct answer: When the motor reaches approximately 75% of its synchronous speed
The potential relay senses back-EMF from the start winding; when the motor reaches about 75% of synchronous speed, back-EMF is high enough to open the relay and drop the start capacitor out of the circuit.
Question 90: Which of the following describes the process occurring within the condenser coil?
- Low-pressure liquid refrigerant boils and absorbs heat.
- High-pressure liquid experiences a sharp pressure drop.
- Low-pressure vapor is compressed into a high-pressure vapor.
- High-pressure vapor refrigerant rejects heat and condenses into a liquid. (Correct answer)
Correct answer: High-pressure vapor refrigerant rejects heat and condenses into a liquid.
The condenser receives high-pressure, high-temperature vapor from the compressor. As outdoor air is blown across the condenser coils, the refrigerant rejects heat to the ambient air, causing it to desuperheat and then condense into a high-pressure liquid.
Question 91: After recharging, a technician notices the AC vent temperature is warmer than expected despite correct refrigerant charge. What component should be inspected next?
- Blower motor speed resistor
- Condenser fins for dirt and blockage (Correct answer)
- Blend door actuator
- High-pressure switch
Correct answer: Condenser fins for dirt and blockage
A clogged or bent condenser prevents adequate heat rejection, raising refrigerant temperature and reducing the system's ability to produce cold air even with a proper charge.
Question 92: What does TXV stand for in an automotive AC system, and what is its function?
- Total Vent Exchange — controls cabin air circulation
- Turbo Exhaust Valve — manages backpressure
- Thermal Expansion Valve — meters refrigerant flow into the evaporator (Correct answer)
- Temperature eXchange Ventilator — regulates condenser temperature
Correct answer: Thermal Expansion Valve — meters refrigerant flow into the evaporator
The Thermal Expansion Valve (TXV) regulates the amount of refrigerant entering the evaporator based on evaporator outlet temperature, optimizing efficiency.
Question 93: What is the purpose of installing a P-trap on a condensate drain line?
- To measure condensate volume
- To filter debris from condensate
- To increase condensate flow rate
- To prevent sewer gases from entering the unit (Correct answer)
Correct answer: To prevent sewer gases from entering the unit
A P-trap creates a water seal that prevents sewer gases and odors from being drawn into the air handler through the drain line.
Question 94: While diagnosing a system, a technician observes low suction pressure, low superheat, and a frosted evaporator coil only near its inlet. Further inspection reveals an abnormally high subcooling reading. What is the most probable diagnosis?
- An overcharged system.
- A severe refrigerant undercharge.
- A restriction in the liquid line filter-drier. (Correct answer)
- A failed indoor blower motor.
Correct answer: A restriction in the liquid line filter-drier.
A restriction before the metering device (like in the filter-drier) causes refrigerant to back up in the condenser, leading to high subcooling. The restriction starves the evaporator of refrigerant, causing a large pressure drop across the blockage. This results in a very low suction pressure and causes the small amount of refrigerant that passes through to flash off and freeze immediately at the evaporator inlet, leading to low superheat readings.
Question 95: A technician finds the compressor running but no cooling occurring and the refrigerant charge appears correct. The metering device is a TXV. What should be checked first?
- Liquid line size
- Condenser coil cleanliness
- TXV bulb contact and charge (Correct answer)
- Evaporator fan motor
Correct answer: TXV bulb contact and charge
A TXV with a lost bulb charge or poor bulb contact will stay closed, preventing refrigerant flow and causing a no-cooling condition.
Question 96: What is the primary reason technicians perform a nitrogen pressure test before evacuating a new AC system?
- To purge contaminants from the lineset
- To test electrical connections under load
- To pre-charge the system with nitrogen
- To identify and locate leaks before pulling a vacuum (Correct answer)
Correct answer: To identify and locate leaks before pulling a vacuum
Nitrogen pressure testing at 150–300 psig reveals leaks at joints and connections before the vacuum process, since a vacuum cannot identify leak locations.
Question 97: How does an orifice tube system differ from a TXV system in refrigerant metering?
- Both are identical in function but differ only in location
- A TXV is used only on electric vehicles
- An orifice tube actively adjusts flow based on temperature; a TXV is fixed
- An orifice tube is a fixed restriction; a TXV dynamically modulates flow based on superheat (Correct answer)
Correct answer: An orifice tube is a fixed restriction; a TXV dynamically modulates flow based on superheat
The orifice tube is a simple fixed-diameter metering device, while the TXV continuously adjusts refrigerant flow to maintain a set superheat at the evaporator outlet.
Question 98: When performing a refrigerant recovery, the technician should recover the refrigerant until the system pressure reaches:
- 10 psig
- 50 psig
- 0 psig or as low as possible (Correct answer)
- 30 psig
Correct answer: 0 psig or as low as possible
EPA regulations require recovering refrigerant to 0 psig or as low as the recovery machine can achieve to minimize emissions.
Question 99: The cause of sporadic AC cooling is being identified. Both the high side and low side pressure gauge readings are displayed intermittently on the gauge set, and the high side occasionally decreases below 100 psi. What is the MOST likely reason for the following?
- Overcharged A/C System
- Damaged compressor reed valve
- Stuck expansion valve (Correct answer)
- Compressor internal leak
Correct answer: Stuck expansion valve
An intermittently stuck expansion valve is the most likely cause of sporadic AC cooling and fluctuating pressure readings. If the valve occasionally restricts flow too much or too little, it will lead to inconsistent refrigerant metering. When it restricts flow excessively, the high-side pressure might drop significantly (below 100 psi) as the compressor struggles to move refrigerant past the blockage, leading to inconsistent cooling.
Question 100: When an AC outdoor unit is installed on a rooftop, the mounting platform must:
- Be constructed of wood for flexibility
- Be structurally rated for the unit weight and allow for vibration isolation (Correct answer)
- Be secured with standard wood screws only
- Be elevated exactly 12 inches above the roof surface
Correct answer: Be structurally rated for the unit weight and allow for vibration isolation
Rooftop installations require structurally adequate, properly rated supports with vibration isolation pads to protect both the unit and the roof structure.
HVAC/R Certification Exam
The HVAC/R Certification Exam exam validates essential knowledge and skills required for certification or licensure in this field.
Exam Rules
- You can skip questions and return to them later
- Flag questions for review before submitting
- No feedback shown until you submit the entire exam
- Unanswered questions count as wrong — answer everything
- 10 pretest questions are mixed in and don't affect your score
- Timer auto-submits when time runs out
- Your progress is auto-saved every 30 seconds
Practice questions written with AI assistance and published by Nathan Beja, founder of Practice Test Geeks. They are not real exam questions. We have not yet matched this exam's facts to an official source, so confirm fees, dates and rules with the exam body. Editorial policy