313D System Installation and Startup Questions and Answers 1 — Questions and Answers
Question 1: During a new split system installation, the technician notes the liquid line is 3/8" and the suction line is 7/8". The line set length is 50 feet. The manufacturer's instructions state the outdoor unit comes pre-charged for a 15-foot line set. What is the most critical next step for the technician regarding the refrigerant charge?
- Add a calculated amount of refrigerant based on the additional line set length and diameter. (Correct answer)
- Release the factory charge and allow the system to run for 30 minutes before checking pressures.
- Recover the factory charge and weigh in a new charge based on the nameplate value only.
- Assume the factory charge is sufficient for the longer line set length.
Correct answer: Add a calculated amount of refrigerant based on the additional line set length and diameter.
Most outdoor units are pre-charged for a standard length, often 15 feet. When the line set exceeds this length, additional refrigerant must be added. The amount is calculated based on the manufacturer's specification (e.g., ounces per additional foot) for the specific liquid line diameter. Failing to add the correct amount will result in an undercharged system, leading to poor performance and potential equipment damage.
Question 2: A technician is performing a deep vacuum evacuation on a newly installed residential air conditioning system. After achieving a vacuum of 400 microns, the technician isolates the system from the vacuum pump. The micron gauge reading slowly rises and then stabilizes at 1,500 microns. What does this indicate?
- There is a small leak in the system.
- The vacuum pump oil is contaminated and needs to be changed.
- The system is leak-free but still contains moisture. (Correct answer)
- The micron gauge is faulty and requires calibration.
Correct answer: The system is leak-free but still contains moisture.
When a deep vacuum is pulled, moisture in the system begins to boil and vaporize. If the system is isolated and the vacuum level rises but then holds steady (e.g., between 1,000 and 2,000 microns), it signifies that the remaining trapped moisture has finished vaporizing, raising the pressure. A continuous, unending rise in pressure would indicate a leak.
Question 3: Which of the following is a critical reason for installing a P-trap at the base of a long vertical suction line riser in a split-system air conditioner installation?
- To prevent liquid refrigerant from flooding the evaporator coil on startup.
- To ensure proper oil return to the compressor. (Correct answer)
- To reduce unwanted noise and vibration during operation.
- To provide a location for future system access and service.
Correct answer: To ensure proper oil return to the compressor.
During operation, a small amount of compressor oil circulates with the refrigerant. In a vertical suction line, gravity can work against the flow of this oil back to the compressor. A P-trap at the base of the riser collects oil, which is then pushed up the riser in slugs by the refrigerant vapor velocity, ensuring the compressor remains properly lubricated. Lack of proper oil return can lead to compressor failure.
Question 4: During the commissioning of a new residential AC system with a TXV metering device, which charging method provides the most accurate results and is recommended by most manufacturers?
- Superheat method, based on indoor wet-bulb and outdoor dry-bulb temperatures.
- Subcooling method, measured at the liquid line service valve. (Correct answer)
- Feeling the suction line temperature by hand to ensure it is 'beer can cold'.
- Setting pressures to a standard chart without considering temperatures.
Correct answer: Subcooling method, measured at the liquid line service valve.
For systems equipped with a Thermostatic Expansion Valve (TXV), the subcooling method is the manufacturer-recommended procedure for accurate charging. The TXV's job is to maintain a constant superheat, so trying to charge by superheat will be inaccurate. Subcooling measures the amount of liquid refrigerant backed up in the condenser, which directly indicates whether the system has the correct refrigerant volume.
Question 5: A technician is installing a new condensing unit on an unlevel gravel bed. What is the proper first step to ensure long-term reliability of the unit?
- Use shims to level the existing gravel bed before placing the unit.
- Pour a new, level concrete pad or install a high-impact plastic pad. (Correct answer)
- Proceed with the installation as the unit's internal components can handle a slight angle.
- Place wooden blocks under the unit's feet to achieve a level position.
Correct answer: Pour a new, level concrete pad or install a high-impact plastic pad.
Condensing units must be installed on a solid, level surface to ensure proper compressor lubrication, fan operation, and cabinet drainage. An unlevel surface can cause premature compressor and fan motor bearing failure. The best practice is to install a dedicated, level equipment pad made of concrete or a durable, weather-resistant plastic.
Question 6: Which of the following documents is essential for determining the correct equipment size and capacity for a new residential air conditioning installation?
- The local building permit application.
- A Manual J load calculation report. (Correct answer)
- The homeowner's previous utility bills.
- The manufacturer's warranty registration form.
Correct answer: A Manual J load calculation report.
A Manual J load calculation is the industry standard method for determining the precise heating and cooling needs of a specific house. It accounts for factors like square footage, insulation levels, window type and orientation, air leakage, and local climate data. Sizing a system based on this calculation ensures optimal performance, efficiency, and comfort, preventing issues like short-cycling or inadequate dehumidification.
During a new split system installation, the technician notes the liquid line is 3/8" and the suction line is 7/8".
The line set length is 50 feet.
The manufacturer's instructions state the outdoor unit comes pre-charged for a 15-foot line set.
What is the most critical next step for the technician regarding the refrigerant charge?