Copper Cabling Flashcards
7 cards from real VDV practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Copper Cabling flashcards as text
When installing copper cabling near fluorescent lighting fixtures, what is the minimum separation distance recommended by TIA-569?
Answer: 5 inches (12.7 cm)
TIA-569 recommends a minimum 5-inch separation between telecommunications cables and fluorescent fixtures to reduce EMI-induced noise.
What is the purpose of the spline or cross-filler found inside some Cat6 cables?
Answer: Maintain pair separation to reduce crosstalk between the four pairs
The internal plastic spline physically separates the four pairs, maintaining consistent geometry that reduces near-end crosstalk in Cat6 cable.
A field tester reports a 'split pair' fault. What wiring error causes this condition?
Answer: One conductor from two different pairs is wired together instead of using a matched pair
A split pair occurs when wires from two different pairs are used together as a pair, destroying the balanced transmission and drastically increasing crosstalk.
Which copper cabling characteristic is expressed in decibels per 100 meters (dB/100m) and represents signal power lost along the cable?
Answer: Insertion loss (attenuation)
Insertion loss, also called attenuation, measures how much signal power is lost as it travels through the cable and is expressed as dB per unit length.
In a T568A vs T568B comparison, which pairs are swapped between the two standards?
Answer: Pairs 2 and 3 (the green and orange pairs)
T568A and T568B differ only in the positions of the orange and green pairs (pairs 2 and 3); all other pairs remain in the same pin positions.
What is the characteristic impedance of standard Cat5e/Cat6 UTP cable?
Answer: 100 ohms
All TIA-568 categories of UTP horizontal cabling have a nominal characteristic impedance of 100 ohms ± 15 ohms.
A VDV technician is testing a newly installed Cat6 link and finds the 'PS-NEXT' value is failing. What does PS-NEXT measure?
Answer: Power Sum NEXT — the combined crosstalk from all disturbing pairs onto one victim pair simultaneously
PS-NEXT (Power Sum NEXT) calculates the total crosstalk noise on a victim pair from all three other disturbing pairs combined, reflecting real-world multi-pair transmission.