Conductors and Cables Flashcards
6 cards from real TN LLE practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 6 Conductors and Cables flashcards as text
Per NEC Table 310.16, what is the ampacity of a 12 AWG THHN copper conductor at 30 degrees C ambient?
Answer: 30 amperes
NEC Table 310.16 lists 12 AWG THHN copper at 30 amperes in the 90 degrees C column.
What is the maximum number of 12 AWG THHN conductors permitted in a 3/4-inch EMT conduit per NEC Chapter 9?
Answer: 12
Per NEC Chapter 9, Annex C, Table C1, a 3/4-inch EMT can hold up to 12 conductors of 12 AWG THHN.
Per NEC 310.15(C)(1), what ampacity adjustment factor applies when 7-9 current-carrying conductors are in a single conduit?
Answer: 70%
NEC Table 310.15(C)(1) requires a 70% ampacity adjustment when 7-9 current-carrying conductors share a raceway.
What is the minimum burial depth for UF cable installed under a residential driveway per NEC Table 300.5?
Answer: 24 inches
Per NEC Table 300.5, direct-buried UF cable under a one- and two-family dwelling driveway requires a minimum cover of 24 inches.
Per NEC 334.80, what limitation applies to NM cable when installed in thermal insulation?
Answer: Ampacity must be based on the 60 degrees C conductor rating
NEC 334.80 requires that the ampacity of NM cable installed in thermal insulation be based on the 60 degrees C conductor temperature rating.
What is the maximum voltage rating for Type NM cable per NEC 334.116?
Answer: 600 volts
NEC 334.116 states that NM cable shall be rated at 600 volts.