TN LLE Cheat Sheet 2026
The 30 highest-yield TN LLE facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.
40 questions
120 min time limit
73% to pass
- Which of the following wiring methods is required for branch circuits serving patient care spaces in a health care facility? → A metal raceway or a cable with a metallic sheath.
- A commercial occupancy has 100 general-purpose duplex receptacles. What is the calculated load for these receptacles after applying demand factors? → 14,000 VA
- What is the minimum burial depth for UF cable installed under a residential driveway per NEC Table 300.5? → 24 inches
- A transformer nameplate shows 5% impedance and 75 kVA rating at 240V secondary. What is the maximum available fault current at the transformer terminals? → 6,250 amperes
- What is the maximum total degrees of bends permitted in a single run of conduit between two pull points (e.g., from one junction box to another)? → 360 degrees
- What is the purpose of motor overload protection separate from the branch circuit breaker? → To protect the motor windings from sustained overcurrent that would cause overheating
- What is the maximum number of 12 AWG THHN conductors permitted in a 3/4-inch EMT conduit per NEC Chapter 9? → 12
- When pulling conductors through a conduit, what is the maximum recommended pulling tension for copper conductors to avoid damage? → 0.008 x cmil per conductor
- In a commercial garage used for major vehicle repair, which area is generally classified as a Class I, Division 2 hazardous location? → The area from the floor up to a level of 18 inches above the floor.
- According to OSHA standards, how often should electrical safety training be provided to employees who work with or near electricity? → Annually
- Per NEC 430.102, a motor disconnecting means must be located where relative to the motor? → Within sight from the motor location and the controller
- According to Tennessee regulations, what is the penalty for performing electrical work without proper licensure? → Civil penalties, potential misdemeanor charges, and requirement to obtain proper licensure
- Type SE (Service Entrance) cable used for branch circuit or feeder wiring inside a building is governed by which NEC article? → NEC Article 338
- A feeder is installed to supply a subpanel in a detached garage. Which of the following is required for the feeder? → It must include an equipment grounding conductor.
- What is the calculated general lighting load for a 20,000 sq. ft. office building after applying all applicable demand factors? → 41,250 VA
- Per NEC 240.86, what is the maximum distance for a series-rated system where the line-side device protects load-side devices? → No distance limit as long as the combination is tested and listed
- Per NEC 210.12, where is AFCI protection required in a dwelling unit? → All areas except bathrooms, garages, and outdoors
- Per NEC 250.30, what grounding requirements apply to a separately derived system such as a transformer? → A system bonding jumper and grounding electrode conductor must be installed at the source
- Per NEC Chapter 9, Table 1, what is the maximum conduit fill percentage for one conductor installed in a raceway? → 53%
- What is the relationship between voltage, current, and resistance known as? → Ohm's law
- Under NEC 300.22(C), wiring installed in a plenum ceiling space used for air handling must: → Use only plenum-rated cables or wiring enclosed in metal conduit
- What is the significance of using a Ground Fault Circuit Interrupter (GFCI) in wet or damp locations? → To prevent electrical shocks
- What is I squared t and why is it important in overcurrent protection? → Current squared times time — measures total energy let-through during a fault
- What conductor type is required for wet locations per NEC 310.10(C)? → Any conductor rated for wet locations such as THWN, XHHW, or USE
- According to Tennessee licensing requirements, can a Limited Licensed Electrician install a central air conditioning system in a new commercial building? → No, this typically requires a full electrical contractor license
- What is the formula for calculating apparent power in a single-phase AC circuit? → S = V x I
- Per NEC 430.6, what current value is used for determining conductor size and overcurrent protection for a motor? → NEC table full-load current values
- Per NEC 110.26(A)(1), what is the minimum clear working space depth in front of electrical equipment operating at 120 to 250 volts (Condition 1)? → 36 inches
- Per NEC 250.122, what is the minimum size equipment grounding conductor for a circuit protected by a 60-ampere overcurrent device? → 10 AWG
- What is the minimum service size required for a single-family dwelling per NEC 230.79(C)? → 100 amperes
Turn these facts into recall: