A rooftop packaged unit condenser fan motor fails in summer. What will happen to system operation if ignored?
Answer: Head pressure will rise, potentially tripping the high-pressure switch or damaging the compressor
Without condenser airflow, heat rejection fails, causing discharge pressure to rise until the high-pressure cutout trips or the system sustains damage.
A technician recovers refrigerant from a system, then pulls a deep vacuum and the vacuum rises rapidly when the pump is isolated. What does this indicate?
Answer: There is a leak or residual moisture in the system
A rising vacuum after pump isolation indicates either a system leak (air entering) or moisture boiling off, both requiring remediation before recharge.
What is the significance of measuring temperature difference (TD) across an evaporator coil during troubleshooting?
Answer: TD measures airflow adequacy and coil heat transfer effectiveness
The temperature difference between air entering and leaving the evaporator reflects airflow volume and coil efficiency; abnormal TD suggests airflow or coil problems.
A refrigeration system uses a capillary tube metering device and is suspected of being undercharged. How is the charge typically verified on this type of system?
Answer: By weighing in the exact factory charge after a complete evacuation
Capillary tube systems are critically charge-sensitive and are best charged by weighing the exact factory specification into an evacuated system.
During troubleshooting, a technician finds that the contactor coil is energized but the compressor does not start. The compressor hums briefly then the internal overload trips. What is the most likely cause?
Answer: Single-phasing (loss of one leg of power) or failed start components
A compressor that hums but fails to start and trips its overload is typically experiencing single-phasing or has failed start capacitors/relays preventing proper motor starting.
A technician suspects a hermetic compressor has an internal motor winding short. Which instrument confirms this diagnosis?
Answer: Megohmmeter (megger) or ohmmeter measuring winding resistance
A megohmmeter measures insulation resistance between windings and ground, confirming a winding short or ground fault in a hermetic compressor motor.
What condition is indicated when a system's sight glass shows clear liquid but system pressures are abnormal (low suction, high discharge)?
Answer: The sight glass location may be downstream of a restriction masking low charge
A restriction such as a blocked filter-drier upstream of the sight glass can back up liquid and show a clear glass even when charge is insufficient.