  1. A refrigeration system has high discharge pressure and high suction pressure. What is the most likely cause?

    Answer: Overcharge of refrigerant

    An overcharge of refrigerant raises both suction and discharge pressures above normal operating levels.

  2. A technician finds oil accumulation in the evaporator of a low-temperature system. What is the most probable cause?

    Answer: Insufficient refrigerant velocity to return oil

    At low temperatures, refrigerant vapor velocity may be too low to carry oil back to the compressor, causing oil to accumulate in the evaporator.

  3. During operation, a system's compressor cycles on and off rapidly (short-cycles). Which condition is the LEAST likely cause?

    Answer: Dirty condenser coil

    A dirty condenser coil raises discharge pressure but does not typically cause rapid short-cycling on the low-pressure control.

  4. A walk-in cooler compressor runs continuously but the box temperature never reaches setpoint. Suction pressure is low and discharge pressure is normal. What should be checked first?

    Answer: Refrigerant charge (undercharge)

    Low suction pressure combined with continuous compressor operation and warm box temperature strongly suggests a refrigerant undercharge.

  5. What does a frost pattern that stops midway through an evaporator coil typically indicate?

    Answer: Partially blocked or malfunctioning expansion device

    A frost pattern ending midway indicates refrigerant is fully evaporating before the end of the coil, suggesting a restricted or undersized expansion device.

  6. A technician measures 15°F of subcooling at the liquid line service valve. Normal subcooling for this system is 10°F. What does this indicate?

    Answer: Refrigerant overcharge or liquid line restriction upstream of measurement point

    Higher-than-normal subcooling suggests an overcharge or a restriction upstream that is backing up liquid refrigerant.

  7. A system exhibits liquid slugging at compressor startup. Which corrective action is most appropriate?

    Answer: Install or verify operation of a crankcase heater

    A crankcase heater prevents refrigerant migration into the oil sump during off-cycles, eliminating liquid slugging at startup.