Refrigerant Management Flashcards
7 cards from real RSES practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Refrigerant Management flashcards as text
Under EPA Section 608, what is the maximum allowable annual leak rate for refrigerant in a commercial refrigeration system containing more than 50 lbs of refrigerant?
Answer: 20%
EPA Section 608 sets the annual leak rate threshold at 20% for commercial refrigeration systems with more than 50 lbs of refrigerant.
Which refrigerant blend is classified as a zeotropic mixture, meaning its components evaporate and condense at different temperatures?
Answer: R-404A
R-404A is a zeotropic blend of R-125, R-143a, and R-134a that exhibits temperature glide during phase change.
When recovering refrigerant from a system with a compressor that is not operational, a technician must use what type of recovery method?
Answer: System-dependent recovery
System-dependent (passive) recovery relies on the system's own components and is only viable when the compressor is operable; with a non-operational compressor, a self-contained recovery unit must be used.
What does the term 'temperature glide' refer to in refrigerant blends?
Answer: The range of temperatures at which a blend changes phase at constant pressure
Temperature glide is the difference between the bubble point and dew point temperatures of a zeotropic blend during phase change at constant pressure.
A recovery cylinder must not be filled beyond what percentage of its rated capacity by weight?
Answer: 80%
DOT regulations require that refrigerant recovery cylinders not be filled beyond 80% of their rated capacity by weight to allow for thermal expansion.
Which organization sets the safety classification system (A1, A2, B1, B2, etc.) for refrigerants used in the HVACR industry?
Answer: ASHRAE
ASHRAE Standard 34 establishes the refrigerant safety classification system using letter-number designations for toxicity and flammability.
R-410A operates at significantly higher pressures than R-22. Approximately how much higher are its operating pressures?
Answer: Twice as high
R-410A operates at approximately twice the pressure of R-22, requiring system components specifically rated for its higher pressure range.