Wiring Methods and Materials Flashcards
6 cards from real 309A practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Wiring Methods and Materials flashcards as text
What is the maximum fill ratio for a conduit containing three or more conductors according to the CEC?
Answer: 40%
CEC Table 8 specifies that conduit containing three or more conductors shall not be filled beyond 40% of the conduit's cross-sectional area to allow for heat dissipation and ease of pulling.
What type of cable is designated TECK90 used for in Canadian electrical installations?
Answer: Exposed industrial wiring in wet or dry locations
TECK90 cable is an armoured cable widely used in Canadian industrial installations. It can be used in wet or dry locations, exposed or concealed, and its interlocking armour provides mechanical protection.
What is the minimum bending radius for a 1-inch rigid metal conduit?
Answer: 6 times the conduit diameter
The CEC requires a minimum bending radius of 6 times the internal diameter for conduits larger than 1/2 inch when using a one-shot bender, to prevent conductor damage and conduit deformation.
Which conductor insulation type is rated for both wet and dry locations at 90°C?
Answer: RW90
RW90 insulation is rated for 90°C in both wet and dry locations. The 'R' indicates it's suitable for raceway use, and 'W' indicates wet location rating.
What is the purpose of a bonding bushing on a conduit entering an electrical panel?
Answer: To ensure electrical continuity across the connection
A bonding bushing ensures a reliable electrical bond between the conduit and the enclosure, providing a low-impedance fault return path. This is critical for proper operation of overcurrent devices.
According to the CEC, what is the minimum cover required for a junction box mounted flush with a non-combustible surface?
Answer: 6 mm maximum gap
CEC Rule 12-3016 permits a maximum gap of 6 mm between the edge of a junction box and the finished non-combustible surface when mounted flush.