Wiring Methods and Materials Flashcards

6 cards from real 309A practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 6 Wiring Methods and Materials flashcards as text
  1. What is the primary advantage of using MC (metal-clad) cable over NMD90 in commercial applications?

    Answer: Mechanical protection from the metal armour

    MC cable's interlocking metal armour provides superior mechanical protection compared to NMD90's non-metallic sheath, making it suitable for exposed commercial and industrial installations.

  2. What is the CEC requirement for supporting NMD90 cable within a distance of an electrical box?

    Answer: Within 300 mm

    CEC Rule 12-510 requires NMD90 cable to be supported within 300 mm of every box, cabinet, or fitting to prevent strain on the connections.

  3. What type of raceway is most suitable for a corrosive chemical processing environment?

    Answer: PVC conduit (Schedule 40)

    PVC conduit is highly resistant to chemical corrosion and is the preferred raceway material in corrosive environments such as chemical processing plants.

  4. What is the maximum percentage fill for a wireway (auxiliary gutter) according to the CEC?

    Answer: 75%

    CEC rules permit wireways to be filled to a maximum of 75% of their cross-sectional area at any point, providing more space than conduit but still allowing for adequate wiring access.

  5. When is it acceptable to use flexible metal conduit (FMC) as the sole equipment grounding conductor?

    Answer: When the conduit is 25 mm trade size or smaller and the circuit is 20 A or less

    The CEC permits FMC to serve as the equipment grounding conductor only when the trade size is 25 mm or smaller and the circuit overcurrent device rating does not exceed 20 A.

  6. What colour identification is required for a high-leg (wild leg) conductor in a 4-wire delta system?

    Answer: Orange

    The CEC requires the high-leg conductor in a 4-wire delta system to be identified by an orange colour marking to warn electricians of its higher-than-expected voltage to neutral.