Transformers and Power Distribution Flashcards
6 cards from real 309A practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 6 Transformers and Power Distribution flashcards as text
What is the standard secondary voltage for a three-phase commercial building service in Canada?
Answer: 347/600 V
The standard three-phase commercial/industrial voltage in Canada is 347/600 V (wye-connected), where 347 V is the phase-to-neutral voltage used for lighting and 600 V is the line-to-line voltage for motors.
What is an autotransformer and what is its main advantage?
Answer: A single-winding transformer with a shared primary/secondary; smaller size and cost
An autotransformer uses a single winding with a tap, sharing conductors between primary and secondary. This makes it smaller, lighter, and less expensive than a two-winding transformer of the same rating.
What voltage would be measured between the high leg and neutral in a 120/240 V four-wire delta system?
Answer: 208 V
In a 4-wire delta system, the high leg (wild leg) to neutral voltage is 240 × (√3/2) = 208 V. This is higher than the normal 120 V phase-to-neutral voltage of the other two phases.
What is the efficiency of a transformer with an output of 45 kW and losses of 2.5 kW?
Answer: 94.7%
Efficiency = Output / Input × 100 = Output / (Output + Losses) × 100 = 45 / (45 + 2.5) × 100 = 45/47.5 × 100 = 94.7%.
What type of transformer winding has the most turns?
Answer: The high-voltage winding always has more turns
The high-voltage winding always has more turns than the low-voltage winding. The voltage ratio is directly proportional to the turns ratio: VP/VS = NP/NS.
What is the purpose of a buck-boost transformer?
Answer: To make small adjustments (typically ±10-20%) to an existing voltage
Buck-boost transformers are small autotransformers used to increase (boost) or decrease (buck) supply voltage by small amounts, typically 5-20%, to correct for voltage variations.