OSHA Safety Standards Flashcards

6 cards from real PC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 6 OSHA Safety Standards flashcards as text
  1. An electrical contractor is setting up a temporary power supply on a construction site. According to OSHA standard 1926.404, what is required for all 120-volt, single-phase, 15- and 20-ampere receptacle outlets on construction sites that are not part of the permanent wiring of the building?

    Answer: They must have ground-fault circuit-interrupter (GFCI) protection.

    OSHA 29 CFR 1926.404(b)(1)(i) requires that for construction sites, all 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring must have ground-fault circuit-interrupter (GFCI) protection for personnel. This is crucial for preventing electrocution in the frequently damp and hazardous conditions of a construction environment.

  2. An electrician is tasked with de-energizing a circuit breaker in a panel to work on a lighting circuit. Which of the following is a key requirement of the OSHA standard for the control of hazardous energy (Lockout/Tagout), 29 CFR 1910.147?

    Answer: A tag may be used by itself only if a lock is not feasible and the employer can demonstrate equivalent protection.

    OSHA's Lockout/Tagout standard (29 CFR 1910.147) allows for the use of a tagout device without a lock only if the device provides a level of safety equivalent to that of a lock and the employer can demonstrate this. In most electrical applications, a lock is considered feasible. The standard's core principle is to ensure the machine or equipment is isolated from all energy sources and rendered inoperative before service or maintenance work is started.

  3. According to OSHA 29 CFR 1926 Subpart K, what is the minimum headroom of working spaces required around electrical equipment like switchboards, panelboards, or motor control centers that are 600 volts, nominal, or less?

    Answer: 6 feet, 3 inches

    OSHA standard 29 CFR 1926.403(i)(2)(i) specifies that the minimum headroom of working spaces about service equipment, switchboards, panelboards, or motor control centers shall be 6 feet 3 inches (1.91 m). This ensures adequate space for an electrician to work safely without being forced into an awkward or dangerous position.

  4. A qualified electrician is working on an energized electrical panel. Which of the following types of personal protective equipment (PPE) is MOST critical according to OSHA standards for protecting against arc flash hazards?

    Answer: Arc-rated clothing and a face shield.

    While other PPE is important, OSHA standards, which often refer to NFPA 70E, require specific arc-rated (AR) clothing, such as shirts, pants, and coveralls, along with an arc-rated face shield or hood, to protect against the extreme temperatures and intense energy of an arc flash. Standard clothing can ignite and cause severe burns, making AR apparel a critical last line of defense.

  5. An electrical contractor's employee needs to use a portable ladder to access an overhead junction box. To comply with OSHA safety standards (29 CFR 1926 Subpart X), which of the following practices is prohibited?

    Answer: Carrying a small tool, like a screwdriver, in one hand while climbing the ladder.

    OSHA requires that employees face the ladder and maintain three points of contact (two hands and a foot, or two feet and a hand) at all times when climbing up or down a ladder. Carrying tools or materials in hand that could cause a loss of balance is a violation of this rule. Tools should be hoisted or carried in a tool belt.

  6. Which of the following best describes the OSHA requirement for 'Guarding of live parts' under 29 CFR 1926.403(i)(2)?

    Answer: Live parts of electric equipment operating at 50 volts or more must be guarded against accidental contact.

    According to OSHA 29 CFR 1926.403(i)(2), live parts of electric equipment operating at 50 volts or more must be guarded against accidental contact. This can be achieved by location in a room accessible only to qualified persons, by permanent partitions or screens, or by elevation of 8 feet or more above the floor.