โ† All PC Flashcard Decks

Load Calculations and Service Entrance Flashcards

6 cards from real PC practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 6 Load Calculations and Service Entrance flashcards as text
  1. Which NEC article covers service conductors and equipment for electrical services?

    Answer: Article 230

    NEC Article 230 covers service conductors and service entrance equipment including disconnecting means and overcurrent protection.

  2. Per NEC Table 220.12, what is the general lighting load volt-ampere value per square foot for commercial office buildings?

    Answer: 3.5 VA per sq ft

    NEC Table 220.12 assigns a general lighting load of 3.5 VA per square foot for office buildings used in branch circuit and feeder calculations.

  3. What is the minimum number of 20-ampere small appliance branch circuits required in a residential kitchen per NEC 210.11(C)(1)?

    Answer: Two 20A circuits

    NEC 210.11(C)(1) mandates a minimum of two 20-ampere small appliance branch circuits to serve receptacle outlets in kitchen areas.

  4. Per NEC Table 220.42, what demand factor applies to the first 3,000 VA of residential lighting load?

    Answer: 100%

    NEC Table 220.42 specifies a 100% demand factor for the first 3,000 VA of residential lighting load; demand factors drop for additional load.

  5. What is the minimum ampere rating for service entrance equipment in a new single-family dwelling per NEC 230.79(C)?

    Answer: 100 amperes

    NEC 230.79(C) requires that the service disconnecting means for a single-family dwelling be rated at not less than 100 amperes.

  6. When sizing a feeder supplying multiple motors, how is the largest motor's FLA factored into the load calculation per NEC 430.24?

    Answer: Added at 125% of its FLA

    NEC 430.24 requires that the largest motor's FLA be included at 125% when calculating the total feeder load for a group of motors.