PART P Cheat Sheet 2026

The 30 highest-yield PART P facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.

40 questions
80 min time limit
60.00% to pass
  1. What colour is the standard outer sheath of twin and earth cable used in UK domestic fixed wiring? Grey
  2. According to BS 7671 18th Edition, what is the maximum disconnection time for a 230V final circuit not exceeding 32A protected by an overcurrent device? 0.4 seconds
  3. During an RCD test, what trip times are acceptable for a 30mA Type AC RCD when tested at rated residual current (IΔn)? Must trip within 300ms
  4. Which of the following is NOT notifiable work under Part P? Replacing a like-for-like socket outlet on an existing circuit in a living room
  5. What is the 'rated current' (In) of an MCB? The maximum continuous current the MCB can carry without tripping
  6. What is the maximum floor area that can be served by a single 32 A ring main circuit in a domestic dwelling? 100 m² (any floor, or individual floors above 100 m² require additional circuits)
  7. What does a Periodic Inspection Report (PIR/EICR) code C2 signify? Potentially dangerous — urgent remedial action required
  8. What is a 'periodic inspection report' now called? Electrical Installation Condition Report (EICR)
  9. What is the purpose of discrimination between protective devices? To ensure only the device closest to the fault operates, leaving other circuits unaffected
  10. What does 'Zs' represent in electrical installation testing? The total earth fault loop impedance of the circuit
  11. What instrument is used to measure the resistance of an earth electrode? An earth electrode resistance tester (using the 3-probe or 4-probe method)
  12. What is Zone 0 in a bathroom? The interior of the bath or shower tray itself — the area always in contact with water
  13. What size bonding conductor is required for supplementary bonding between two extraneous-conductive-parts (e.g., two metal pipes)? 2.5mm² if mechanically protected, 4mm² if not
  14. According to BS 7671 Section 701, what is the extent of Zone 1 in a bathroom with a bath? The area directly above the bath tub to a height of 2.25m from the floor
  15. According to BS 7671 Section 722, what additional protection is required for EV charging installations in domestic properties? 30mA RCD protection, and depending on the charger type, a Type A or Type B RCD
  16. What standard specifies requirements for consumer units in domestic installations? BS EN 61439-3 (consumer units for household and similar applications)
  17. What Type of MCB is most commonly used for a ring main circuit in a domestic installation? Type B 32 A MCB
  18. Part P applies to electrical installations in which type of building? Dwellings and their associated gardens, outbuildings and shared amenities
  19. Which edition of the IET Wiring Regulations (BS 7671) is the current standard referenced by Part P? 18th Edition (Amendment 2)
  20. Which of the following is NOT a recognised competent person scheme for self-certification of electrical work under Part P? City & Guilds
  21. What is the minimum cross-sectional area of the earthing conductor connecting the MET to the earth electrode in a TT system? 6mm² copper if mechanically protected, 16mm² if not
  22. When testing the continuity of a ring final circuit, what is the expected result at the socket furthest from the consumer unit? Approximately 25% of the end-to-end resistance (r1 + r2)/4
  23. How does the zone apply in a bathroom where the ceiling height is less than 2.25 m? Zone 1 extends to the ceiling regardless of whether the ceiling height is below 2.25 m
  24. What is the maximum continuous conductor operating temperature for standard PVC insulated and sheathed cables (e.g., twin and earth)? 70°C
  25. What is the recommended EICR interval for a privately rented domestic property? Every 5 years or at each change of tenancy
  26. What is the minimum cross-sectional area of a supplementary bonding conductor between two exposed conductive parts? 2.5 mm² if mechanically protected, 4 mm² if not mechanically protected
  27. Following the 2004 harmonisation with European cable colour standards, what colour is the line conductor in UK fixed wiring? Brown
  28. What type of RCD detects both AC and pulsating DC residual currents? Type A RCD
  29. What is the recommended minimum burial depth for a cable installed under a domestic garden or lawn (not subject to vehicle traffic)? 500 mm
  30. What is the minimum IP rating for electrical equipment installed outdoors in a domestic garden? IPX4 (splash-proof) minimum, with higher ratings where directly exposed to rain
Turn these facts into recall: