Part P Consumer Unit Replacement 4 — Questions and Answers
Question 1: What is the recommended height for the consumer unit main switch in a domestic installation per accessibility guidance?
- 1.35–1.5 m above finished floor level (to the centre of the main switch operating mechanism) (Correct answer)
- 0.5 m above floor
- 2.5 m above floor
- At floor level
Correct answer: 1.35–1.5 m above finished floor level (to the centre of the main switch operating mechanism)
Accessibility guidance (BS 8300 and NHBC) recommends the consumer unit main switch be at a height (typically 1.35–1.5 m to the switch centre) where it can be reached by most users, including those with limited mobility.
Question 2: What information must the circuit chart inside the consumer unit show?
- Each circuit's purpose, cable reference method, protective device type and rating, and RCD assignment (Correct answer)
- Only the fuse ratings
- Only the circuit numbers
- Only which RCD each circuit is on
Correct answer: Each circuit's purpose, cable reference method, protective device type and rating, and RCD assignment
BS 7671 Regulation 514.9.1 requires a circuit chart (schedule) to be fixed at or adjacent to the consumer unit, showing each circuit's purpose, protective device details, cable size/reference method, and RCD or RCBO assignment.
Question 3: What is the first step when replacing a consumer unit safely?
- Isolate the supply at the cut-out (service fuse) — which requires the electricity supplier's presence or a service cut-out sealing tool — and prove dead before any work begins (Correct answer)
- Switch off the main switch only
- Switch off all MCBs
- Disconnect the meter tails
Correct answer: Isolate the supply at the cut-out (service fuse) — which requires the electricity supplier's presence or a service cut-out sealing tool — and prove dead before any work begins
The supply must be isolated at the cut-out (supply fuse) to make the meter tails and main switch terminals dead before they can be safely disconnected; this requires the electricity supplier to attend or a licensed operative with a sealing tool.
Question 4: What are 'meter tails'?
- The cables connecting the electricity meter to the consumer unit main switch — typically 25 mm² or 35 mm² insulated single-core cables (Correct answer)
- The cables entering the electricity meter from the street
- The cables connecting the consumer unit to individual circuits
- The neutral and earth conductors in the consumer unit
Correct answer: The cables connecting the electricity meter to the consumer unit main switch — typically 25 mm² or 35 mm² insulated single-core cables
Meter tails are the single-core insulated cables connecting the electricity supplier's meter to the consumer unit main switch; they are live when the supply is connected and typically 25–35 mm² cross-section for a standard 100 A supply.
Question 5: Can the meter tails be extended or modified by an electrician during consumer unit replacement?
- Meter tails can be extended or modified by a DNO-registered or competent electrician, but the service fuse and supply-side equipment must not be touched without the DNO's involvement (Correct answer)
- Meter tails can be modified by any Part P registered electrician without restriction
- Meter tails cannot be modified under any circumstances
- Meter tails can only be modified by the electricity supplier
Correct answer: Meter tails can be extended or modified by a DNO-registered or competent electrician, but the service fuse and supply-side equipment must not be touched without the DNO's involvement
Meter tails (between meter and consumer unit) are within the scope of the customer's installation and can be modified by a competent electrician; however, the supply-side (service cable, cut-out and meter) must not be interfered with without the DNO's permission.
Question 6: What type of cable gland is used when a steel-armoured supply cable enters a metal consumer unit?
- An armoured cable gland that clamps the cable armour, providing both strain relief and continuity of the metal enclosure's protection (Correct answer)
- A standard PVC cable gland
- Any gland of sufficient size
- No cable gland is needed for armoured cables
Correct answer: An armoured cable gland that clamps the cable armour, providing both strain relief and continuity of the metal enclosure's protection
Armoured cables (e.g., SWA — steel wire armour) entering a metal consumer unit must use a purpose-made armoured cable gland that clamps the armour, providing mechanical protection, strain relief, and earthing of the armour through the gland.
What is the recommended height for the consumer unit main switch in a domestic installation per accessibility guidance?