A technician performs a contact resistance test on a 3-phase, low-voltage power circuit breaker. The readings are: Phase A = 25 µΩ, Phase B = 30 µΩ, Phase C = 45 µΩ. According to NETA MTS standards, what is the proper evaluation of these results?
-
A
The deviation between phases is acceptable.
-
B
Phase C is unacceptable as it deviates by more than 50% from the lowest reading.
-
C
All phases are unacceptable because the readings exceed 30 µΩ.
-
D
The test is invalid and must be repeated with a higher test current.