An engineer is commissioning a new boiler with a manufacturer's stated gross heat input of 24 kW. Using a metric meter, they time the gas consumption and record that it takes 135 seconds to burn 0.1 m³. The declared calorific value (CV) of the natural gas is 40.0 MJ/m³. How does the calculated heat input compare to the manufacturer's specification?
-
A
It is significantly above the acceptable tolerance of +/- 5%.
-
B
It is within the acceptable tolerance of +/- 5%.
-
C
It is significantly below the acceptable tolerance of +/- 5%.
-
D
The calculation cannot be completed without the net heat input value.