A 3-phase, 480V motor has a full-load current (FLC) of 65A per Table 430.250. The branch circuit will be protected by an inverse-time circuit breaker. According to NEC 430.52(C)(1), what is the MAXIMUM standard size circuit breaker permitted for short-circuit and ground-fault protection?
-
A
150A
-
B
175A
-
C
200A
-
D
125A