An energy auditor is reviewing the Building Automation System (BAS) trend data for a multi-zone Variable Air Volume (VAV) system. The auditor notes that the supply fan maintains a constant duct static pressure of 2.5 inches w.c. at all times, regardless of the building load. What is the most effective energy conservation measure to recommend?
-
A
Implement a duct static pressure reset strategy.
-
B
Increase the chilled water supply temperature setpoint.
-
C
Calibrate all the VAV box damper actuators.
-
D
Replace the existing supply fan with a larger one.