An energy auditor performs a blower door test on a small commercial building and measures an airflow rate of 2,500 cubic feet per minute at a pressure of 50 Pascals (CFM50). If the building's interior volume is 150,000 cubic feet, what is the leakage rate expressed as Air Changes per Hour at 50 Pascals (ACH50)?
-
A
0.6 ACH50
-
B
60.0 ACH50
-
C
1.0 ACH50
-
D
0.017 ACH50