Inspection and Testing Flashcards
6 cards from real NICET practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 6 Inspection and Testing flashcards as text
What does an inspector's test valve simulate in a sprinkler system?
Answer: Operation of a single sprinkler head at the end of the most remote branch line
The inspector's test valve simulates the flow of one sprinkler head at the hydraulically most remote point to test the alarm systems.
How often must fire extinguisher inspections be conducted according to NFPA 10?
Answer: Monthly
NFPA 10 requires portable fire extinguishers to be inspected monthly to verify they are in their designated place and ready to operate.
What is the purpose of a trip test on a pre-action system?
Answer: Verify the detection system releases the pre-action valve correctly
The pre-action system trip test activates the detection system to verify the pre-action valve releases and allows water into the piping.
According to NFPA 25, how often must backflow preventers on fire protection systems be tested?
Answer: Annually
NFPA 25 requires backflow preventers on fire protection system water supplies to be tested annually to ensure they prevent contamination of the potable water supply.
What action is required when a sprinkler system is found out of service during an inspection?
Answer: Immediately notify the property owner and AHJ and implement a fire watch
When a sprinkler system is out of service, the property owner and authority having jurisdiction must be notified immediately and a fire watch must be established.
Which NICET certification level is typically required to supervise inspection and testing of fire alarm systems?
Answer: Level III
NICET Level III is typically required to supervise fire alarm inspection and testing activities and sign off on inspection reports.