NFPA NFPA 72 Fire Alarm Systems 1 — Questions and Answers
Question 1: Under NFPA 72, what is the maximum allowable sound level for a public mode audible alarm signal in a sleeping area?
- 55 dB(A)
- 70 dB(A)
- 75 dB(A) (Correct answer)
- 110 dB(A)
Correct answer: 75 dB(A)
NFPA 72 requires that public mode audible alarms produce a sound level of at least 75 dB(A) at the pillow in sleeping areas.
Question 2: According to NFPA 72, what is the maximum spacing for heat detectors with a listed spacing of 50 feet in a smooth ceiling room?
- 30 feet
- 50 feet (Correct answer)
- 70 feet
- 100 feet
Correct answer: 50 feet
NFPA 72 permits heat detectors to be installed at their listed spacing, which in this case is 50 feet between detectors on a smooth ceiling.
Question 3: Under NFPA 72, which initiating device is classified as a spot-type smoke detector?
- Linear beam detector
- Duct smoke detector
- Ionization smoke detector (Correct answer)
- Air sampling detector
Correct answer: Ionization smoke detector
An ionization smoke detector is a spot-type detector that responds to products of combustion in its immediate vicinity.
Question 4: According to NFPA 72, what is the maximum allowable supervisory signal response time from the control unit to the supervising station?
- 30 seconds
- 60 seconds
- 90 seconds
- 5 minutes (Correct answer)
Correct answer: 5 minutes
NFPA 72 requires that supervisory signals be received at the supervising station within 5 minutes of occurrence.
Question 5: Under NFPA 72, what minimum standby battery capacity is required for a fire alarm control unit?
- 4 hours alarm + 4 hours standby
- 24 hours standby + 5 minutes alarm (Correct answer)
- 4 hours standby + 15 minutes alarm
- 60 minutes alarm only
Correct answer: 24 hours standby + 5 minutes alarm
NFPA 72 requires fire alarm control units to have battery backup for 24 hours in standby followed by 5 minutes in full alarm.
Question 6: According to NFPA 72, where must a remote annunciator panel be located?
- At the main electrical panel
- At a location approved by the authority having jurisdiction (Correct answer)
- Adjacent to the main fire alarm control unit
- In the mechanical room
Correct answer: At a location approved by the authority having jurisdiction
NFPA 72 requires remote annunciator panels to be located where approved by the authority having jurisdiction (AHJ).
Under NFPA 72, what is the maximum allowable sound level for a public mode audible alarm signal in a sleeping area?