NFPA Cheat Sheet 2026

The 30 highest-yield NFPA facts, distilled from real exam questions. Print it, save it as a PDF, or study it here — free, no sign-up.

100 questions
240 min time limit
70% to pass
  1. What does NFPA 72 specify as the maximum travel distance to a manual pull station in an educational occupancy? 150 feet
  2. Under NFPA 25, what is the required testing frequency for antifreeze solution concentration in a sprinkler system? Annually
  3. In the NEC, what does the term "ampacity" refer to? The current-carrying capacity of a conductor
  4. What shape is used for the NFPA 704 hazard identification system placard? Square rotated 45 degrees (diamond)
  5. According to NFPA 25, what is the minimum hydrostatic test pressure for a new sprinkler system installation? 150 psi or 50 psi above maximum system pressure, whichever is greater
  6. Under NFPA 10, what condition automatically requires a fire extinguisher to be hydrostatically tested? After any use, full or partial discharge
  7. Under NFPA 25, what must be done with recorded inspection, testing, and maintenance (ITM) reports? Retained for the life of the system and made available to the AHJ
  8. According to NFPA 1, what is the minimum illumination level required at the floor of a means of egress during normal operation? 1 footcandle
  9. According to NFPA 30, what is required around above-ground flammable liquid tanks to contain spills? Secondary containment capable of holding 100% of the largest tank volume
  10. Under NFPA 13, what hazard classification applies to auto showrooms, bakeries, and laundries? Ordinary hazard Group 1
  11. An instability rating of 4 in NFPA 704 indicates the material: Is readily capable of detonation or explosive decomposition at normal temperatures
  12. In NFPA 704, a flammability rating of 2 applies to liquids with a flash point in which range? Between 100°F and 200°F (37.8–93.3°C)
  13. According to the NFPA Life Safety Code, what is the minimum width requirement for egress doors in new buildings? 32 inches
  14. According to NFPA 1, what must a fire safety and evacuation plan include? Emergency procedures, staff assignments, evacuation routes, and training requirements
  15. Under NFPA 72, what is the maximum height above the floor at which a manual pull station may be installed? 60 inches
  16. Under NFPA 72, what is the purpose of a Class A wiring style for initiating device circuits? Allow continued operation after a single open or ground fault
  17. According to NFPA 1, what action must the responsible party take when a fire inspector identifies a code violation? Correct the violation within the timeframe specified by the AHJ
  18. What does the symbol 'SA' in the white section of an NFPA 704 diamond indicate? Simple asphyxiant gas
  19. According to NFPA 30, what type of electrical equipment is required in a flammable liquid storage room classified as a Division 1 hazardous location? Explosion-proof or intrinsically safe
  20. According to NFPA 13, what is the maximum area of sprinkler operation (design area) for a light hazard hydraulically designed system? 1,500 sq ft
  21. According to NFPA 25, what action is required when a sprinkler head shows signs of corrosion, paint, or loading? Replace the sprinkler head immediately
  22. What is the minimum required flow pressure at the most remote sprinkler in an NFPA 13 light hazard system? 10 psi
  23. Which of the following is required for all kitchen countertop outlets according to the NEC? Ground-Fault Circuit Interrupters (GFCIs)
  24. According to the NFPA Life Safety Code, how often should fire drills be conducted in healthcare facilities? Quarterly
  25. Under NFPA 1, what is the maximum rise for a single step in a means of egress? 8.25 inches
  26. Under NFPA 25, what is the required frequency for a full flow trip test of a dry pipe valve? Annually
  27. Under NFPA 1, exit signs must be illuminated to what minimum luminance? 25 footlamberts
  28. Under the NFPA Life Safety Code, what is the maximum travel distance to an exit in a sprinklered educational occupancy? 250 feet
  29. Under NFPA 13, a deluge system differs from a preaction system in that a deluge system has: Open sprinkler heads throughout
  30. Under NFPA 13, what type of sprinkler system uses air pressure to hold water back until a sprinkler activates? Dry pipe system
Turn these facts into recall: